Table of Contents Table of Contents
Previous Page  22 / 320 Next Page
Information
Show Menu
Previous Page 22 / 320 Next Page
Page Background

Data is subject to errors and technical modifications.

1.7

Invicta 3 250A TP&N Distribution Boards (250A Incoming, 63A Outgoing)

200A Tri Metered Boards (Power, Lighting & Mechanical Services)

Incomer Kits for 250A Boards

Characteristics:

-

-

Surface mounted steel enclosures, IP3XD rated, available with plain, glazed & Amendment 3 door options.

-

-

Conforms to BS EN 61439-3. I nA = 250A, I nc = 63A, I cc = 25kA.

-

-

Supplied without incoming and outgoing devices. A Hager incoming kit must be used.

-

-

For dimensions see page

1.48.

Characteristics:

-

-

Provides separate energy information for each group of outgoing devices.

-

-

Boards are supplied with meters that offer a pulsed & modbus output.

-

-

Provided with a 200A incomer pre-fitted with ample cable space.

-

-

Conforms to BS EN 61439-3. I nA = 200A, I nc = 63A, I cc = 25kA.

-

-

For dimensions see page

1.51.

Description

Cat ref.

Plain door

Cat ref.

Glazed door

Cat ref.

Amd 3 Compliant

8 Triple Pole Ways 250A TP&N Board

JK208B

JK208BG

JK208BA3

1

12 Triple Pole Ways 250A TP&N Board

JK212B

JK212BG

JK212BA3

1

16 Triple Pole Ways 250A TP&N Board

JK216B

JK216BG

JK216BA3

1

18 Triple Pole Ways 250A TP&N Board

JK218B

JK218BG

JK218BA3

1

24 Triple Pole Ways 250A TP&N Board

JK224B

JK224BG

JK224BA3

1

Description

Max cable

cap. solid

Lower

pan ways

Middle

pan ways

Upper

pan ways

Cat ref.

8+8+4 Way Power, Lighting & Service Board M8 Lug 8

8

4

JKD2884PM

Description

Connection

Cat ref.

3 Pole 250A MCCB Incomer Kit (Fits within distribution board)

M8 Lug

JK22503M

4 Pole 250A MCCB Incomer Kit (Fits within distribution board)

M8 Lug

JK22504M

3 Pole 250A Switch Disconnector Incomer Kit (Fits within distribution board)

M8 Lug

JK22503S

4 Pole 250A Switch Disconnector Incomer Kit (Fits within distribution board)

M8 Lug

JK22504MCS

4 Pole 250A Direct Connection Kit (Fits within distribution board)

M8 Lug

JK22504D

4 Pole 160A Contactor Incomer Kit includes Switch Disconnector

(fits below distribution board, 450mm high)

M8 Lug

JK21604C

3 Pole 125A MCCB Incomer Kit (Fits within distribution board)

M8 Lug

JK21253M

4 Pole 125A MCCB Incomer Kit (Fits within distribution board)

M8 Lug

JK21254M

JK206BG

JKD2884PM

Type B Distribution Boards

Invicta 3 250A, Metered Boards, Incomer Kits

¹ Full metal cover & door to comply

with BS 7671 Amendment 3.

MCBs & RCBOs for Invicta 3 Type B Distribution Boards -

See pages

1.27- 1.33

for more info

0.5A

1A

2A

3A

4A

6A

10A

B Curve

Single Pole

-

-

-

-

-

NBN106A

NBN110A

Triple Pole

-

-

-

-

-

NBN306A

NBN310A

C Curve

Single Pole

NCN100A

NCN101A

NCN102A

NCN103A

NCN104A

NCN106A

NCN110A

Triple Pole

NCN300A

NCN301A

NCN302A

NCN303A

NCN304A

NCN306A

NCN310A

D Curve

Single Pole

NDN100A

NDN101A

NDN102A

NDN103A

NDN104A

NDN106A

NDN110A

Triple Pole

NDN300A

NDN301A

NDN302A

NDN303A

NDN304A

NDN306A

NDN310A

RCBO (B)

Single Pole

-

-

-

-

-

ADB106

ADB110

RCBO (C)

Single Pole

-

-

-

-

-

ADC106

ADC110

Commercial

Distribution