2.57
Data is subject to errors and technical modifications.
Modular Devices
& Enclosures
Contactors & Relays
Technical Data
Lamp Power 16A 25A
16A + 25A + 40A 63A
Compact fluo lamps
Compact fluo lamp with external electronic ballast
5W
11
15
17
27
49
76
7W
11
15
17
27
49
76
9W
9
13
16
26
40
63
11W
9
13
16
26
40
63
15W
7
11
14
22
36
57
18W
7
11
14
22
36
57
20W
7
11
14
22
36
57
23W
7
11
14
22
36
57
26W
7
11
14
22
36
57
Compact fluo lamp with integrated electronic ballast
5W
17
27
34
54
86
135
7W
17
27
34
54
86
135
9W
17
27
34
54
86
135
11W
17
27
34
54
86
135
15W
17
27
34
54
86
135
18W
13
20
25
40
63
100
20W
13
20
25
40
63
100
23W
13
20
25
40
63
100
26W
13
20
25
40
63
100
Incandescent lamps
Tungsten & halogen lamps 230V
40W
32
50
36
57
76
120
60W
21
33
28
45
67
105
75W
17
27
24
38
63
100
100W 13
20
17
28
41
65
150W 8
13
11
18
29
45
200W 6
9
8
14
22
35
300W 4
7
6
10
15
23
500W 2
3
3
6
9
14
1000W 0
0
1
2
4
7
Tungsten & halogen lamps 12 ou 24V
20W
13
20
25
40
139
218
35W
8
13
16
26
82
129
50W
6
9
11
18
60
94
75W
4
6
7
12
52
82
100W 2
3
3
6
35
55
150W 1
2
2
4
20
31
LED
LED 230V with integrated electronic ballast - non dimmable 4W
17
27
34
54
86
135
4.5W
17
27
34
54
86
135
6W
17
27
34
54
86
135
7W
17
27
34
54
86
135
8W
17
27
34
54
86
135
12W
17
27
34
54
86
135
17W
13
20
25
40
63
101
18W
13
20
25
40
63
101
22W
13
20
25
40
63
101
30W
9
14
17
28
44
70
34W
9
14
17
28
44
70
40W
9
14
17
28
44
70
50W
7
11
14
22
35
55
LED 230V with integrated electronic ballast - dimmable
4W
38
60
76
120
159
250
5.5W
38
60
76
120
159
250
6W
38
60
76
120
159
250
7W
38
60
76
120
159
250
8W
38
60
76
120
159
250
12W
38
60
76
120
159
250
17W
28
44
56
88
118
185
18W
28
44
56
88
118
185
22W
28
44
56
88
118
185
30W
20
31
39
62
82
130
34W
20
31
39
62
82
130
40W
20
31
39
62
82
130
50W
16
24
30
48
65
102
LED 230V headlight with integrated electronic ballast
100W -
-
3
5
6
9
150W -
-
1
3
4
6
200W -
-
1
2
4
6
LED 12V with separated transformer - dimmable
1W
38
60
76
120
180
220
2.5W
38
60
76
120
180
220
4W
38
60
76
120
180
220
5W
38
60
76
120
180
220
7W
38
60
76
120
160
200
10W
38
60
76
120
160
200
15W
28
44
56
88
160
200
Lighting systems with electronic ballasts cause inrush current peaks. Therefore we recommend you use the chart below to determinate the maximum amount of
lamps that can be connected to a Hager contactor: The chart gives the maximum amount of lamps per contact. In 2014 the performances of the contactors in
combination with lights increased. The products identified on the front face with the ‘+’ can accept a higher number of lamps. For these products, see the figures
in the column with the ‘+’ in the header.