Table of Contents Table of Contents
Previous Page  183 / 320 Next Page
Information
Show Menu
Previous Page 183 / 320 Next Page
Page Background

2.56

Data is subject to errors and technical modifications.

Modular Devices

& Enclosures

Contactors & Override Contactors

Technical Data

Description

Modular contact

Auxiliary

contact

Standard conformity

EN 61095

Approvals

NF - VDE- IMQ - KEMA - RMC / CCC

Relay

Contactor Relay

Contactor Contactor Contactor Contactor

Number of modules

1

2

3

½

Thermal current lth (40ºC)

16A

25A

16A

25A

40A

63A

6A

Rated frequency

50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz

Rated insulation voltage (U i )

250V

250V

440V

440V

440V

440V

250V

Rated impulse withstand voltage (U imp )

4kV

4kV

4kV

4kV

4kV

4kV

4kV

Protection Degree

2

2

2

2

2

2

2

Rated Operating currents and power ratings in AC

AC-1 / AC-7a

Rated operational currents Ie

16A

16A

16A

25A

40A

63A

-

Rated operational power 230V

3kW 4.6kW 3kW 4.6kW 7.3kW 11.6kW -

400V

-

-

8.9kW 13.8kW 22kW 35kW -

AC-3 / AC-7b

Rated operational currents Ie

5.5A

8.5A

5.5A

8.5A

25A

32A

-

Rated operational power 230V

570W 880W 570W 880W 2.6kW 3.3kW -

400V

-

-

1.7kW 2.6kW 7.8kW 10kW -

AC-12

Rated operational currents i.e. @ 230V -

-

-

-

-

-

6A

AC-15

Rated operational currents i.e. @ 230V -

-

-

-

-

-

2A

Mechanical and Electrical Endurances

Mechanical endurance

Number of

operations

1,000,000 1,000,000 1,000,000 1,000,000 1,000,000 1,000,000 1,000,000

Electrical endurance @ Ie AC7a (AC12 for aux

contact)

Number of

operations

60,000

60,000

60,000

60,000

60,000

60,000

60,000

MCB Protected short-circuit withstand

Prospected short-circuit current

rms

1kA

3kA

1kA

3kA

3kA

3kA

1kA

Associated protection

MCB C16-

6kA

MCB C25-

6kA

MCB C16-

6kA

MCB C25-

6kA

MCB C40-

10kA

MCB C63-

10kA

6A 10x38

gG Fuse

Power dissipation

Power dissipation per current path

1W 1.5W 1W 1.5W 3.2W 5W 0.4W

Magnetic system for Eco and standard contactor

Pick-up

2.2W 2.2W 2.8W 2.8W 5W 5W -

Coil consumption

2.2W 2.2W 2.8W 2.8W 5W 5W -

Closing delay

25ms

25ms

25ms

25ms

25ms

25ms

-

Opering delay

15ms

15ms

15ms

15ms

20ms

20ms

-

Connection

Main contact cable section

Rigid

1...10mm

2

1...10mm

2

1...10mm

2

1...10mm

2

4...25mm

2

4...25mm

2

1...6mm

2

Flexible

1...6mm

2

1...6mm

2

1...6mm

2

1...6mm

2

4...16mm

2

4...16mm

2

1...6mm

2

Main contact connection screw

Type

M3.4

M3.4

M3.4

M3.4

M5

M5

M3.4

Posidrive PZ2

PZ2

PZ2

PZ2

PZ2

PZ2

PZ2

Max. tight.

torque

1.2Nm 1.2Nm 1.2Nm 1.2Nm 2Nm 2Nm 1.2Nm

Coil connection cable section

Rigid

1...10mm

2

1...10mm

2

1...10mm

2

1...10mm

2

1...10mm

2

1...10mm

2

-

Flexible

1...6mm

2

1...6mm

2

1...6mm

2

1...6mm

2

1...6mm

2

1...6mm

2

-

Coil connection screw

Type

M3.5

M3.5

M3.5

M3.5

M4

M4

-

Posidrive PZ2

PZ2

PZ2

PZ2

PZ2

PZ2

-

Max. tight.

torque

1.2Nm 1.2Nm 1.2Nm 1.2Nm 1.5Nm 1.5Nm -

Working temperature

-10ºC to +50ºC

Storage temperature

-40ºC to +80ºC