2.42

Data is subject to errors and technical modifications.

Modular Devices

& Enclosures

Multifunction Meters - ECM01

Technical Data

Dimensions Diagram (mm)

Voltage

line to neutral and average

Current

phase and average

Current

Maximum Demand

THD Current

phase and average

Power Factor

3-phase and average

Voltage

line to line and average

THD Voltage

line to neutral and average

THD Voltage

line to line and average

Voltage

current and power factor

of phase 1 & frequency

Voltage

current and power factor

of phase 2 & frequency

Voltage

current and power factor

of phase 3 & frequency

Average Voltage

current and power factor

of 3-phases & frequency

Button Selection

Active Power

3-phase and total

Reactive Power

3-phase and total

Apparent Power

3-phase and total

Active, Reactive, Apparent

Power and Power Factor

first phase

Active, Reactive, Apparent

Power and Power Factor

second phase

Active, Reactive, Apparent

Power and Power Factor

third phase

Total Active, Reactive, Apparent

Power & Average Power Factor

three phases

Active Energy

3-phases

Apparent Energy

3-phases

Reactive Energy

3-phases

Max. Active Power Demand,

Reactive Power Demand and

Apparent Power Demand

Min. Active Power Demand

and Reactive Power Demand

ECM01

50

5

91.5

96

91.5

96

Please allow space at the rear of the meter for cable connections.

Function Diagram

-- 96 x 96mm Flush mounting

-- Single phase or 3 phase 4 wire network

balanced or unbalanced load

-- Built in energy pulsed output or with pulsed

output and RS485 (modbus)

-- Backlit LCD display with bargraph current

indication on every page

-- Automatic or manual scrolling display

-- 330mV current transformer input

-- Active energy class 1 (EN62053-21)

-- Reactive energy class 2 (EN62053-23)

-- Programmable VT ratio

-- 3-phase: 140…460Vac measured voltage

-- Single phase: 80…265Vac measured voltage

-- THD up to 31st harmonic for voltage and current

-- Self supplied auxiliary

-- Programmable CT ratio 5 to 10,000A

-- Frequency 45/65Hz

-- Wide range of measured parameters (see table

below)

-- Selectable CT phase correction allows reversal

of L1 and L3

-- Single CT Connection

-- Weight 230g