Table of Contents Table of Contents
Previous Page  168 / 320 Next Page
Information
Show Menu
Previous Page 168 / 320 Next Page
Page Background

2.41

Data is subject to errors and technical modifications.

Modular Devices

& Enclosures

Multifunction Meters

Technical Data

SM101E

SM101C

Current (TRMS)

I (1

st

CT)

5A...9999A

I (2

nd

CT)

5A

In

Calculated

Minimum measuring current (2

nd

CT)

5mA

Input consumption

<0.6VA per phase

Permanent overload (2

nd

CT)

6A

Accuracy

±0.2%

THD

±1%

Update period

1s

Voltage (TRMS)

U

50V a.c....520V a.c. (Ph-Ph)

28V a.c....300V a.c. (Ph-N)

Input consumption

<0.1VA per phase

Permanent overload (2

nd

CT)

760V a.c.

Accuracy

±0.2%

THD

±1%

Update period

1s

Power

Accuracy (P,Q)

±0.5%

Accuracy (S)

±1%

Accuracy (PF)

±0.02%

Update period

1s

Energy

Accuracy (Ea)

Class 0.5s

Accuracy (Er)

Class 2

Update period

1s

Frequency

F

45Hz...65Hz

Accuracy

±0.1%

Update period

1s

Supply

Voltage

200V a.c....277V a.c. ±15%

Frequency

50/60Hz

Consumption

<5VA

Environment

Protection degree

IP51 (front panel)

IP20 (case)

Operating temperature

-10ºC to +55ºC

Storage temperature

-20ºC to +70ºC

Insulation category

III (300V a.c. Ph-Ph)

Degree of pollution

PD2

Communication

Metrological LED

N/A

0.1Wh / pulse

Pulse output

N/A

30V d.c. / 27mA Max

Communication

N/A

RS485

2/3 wires half duplex

Jbus/Modbus

2,400bds...38,400bds

Parity (no,odd,even)

1 or 2 Stop bytes

Connection

Network

1BL

2BL

3BL/3NBL

4BL/4NBL

Current/Voltage input

4mm

2

(solid or stranded)

Others

2.5mm

2

(solid or stranded)

Max torque

0.6Nm

Shape

Weight

205g

215g

Size

4M, 73mm x 90mm x 67mm