7

Switch Disconnectors

3KL Switch Disconnectors with Fuses up to 800 A

Introduction

7/69

Siemens LV 10 · 2014

Technical specifications

1)

Technical specifications for approval on request.

2)

Configuring note: Max. permissible operating temperature

for fuse blades 135 °C, for connections 100 °C.

3)

110 V (one conducting path).

4)

With 3KL61 for operation -25 °C ... +35 °C, at +55 °C:

I

th

= 570 A.

5)

With 3ND1 switchgear protection fuse.

6)

AC-23B.

7)

220 V DC (L1 and L3 series-connected) or 110 V DC

(one conducting path) at DC-23A.

8)

At 440 V

L/R

= 4 ms, at 220 V

L/R

= 15 ms.

9)

Only DC-22A (

L/R

= 2.5 ms).

10)

At 440 V DC-22A, at 220 V DC-23A.

Note:

For the 3KL switch disconnectors, complete kits for standard

and EMERGENCY-STOP application are available for installation

in the side and rear panels of control cabinets.

Standards

IEC 60947-1, IEC 60947-3, VDE 0660 Part 107

Type

3KL50 3KL52

1)

3KL53

1)

3KL55

1)

3KL57

1)

3KL61

1)

3KL62

1)

Rated uninterrupted current

I

u

A 63

125

160

250

400

630

800

For fuse links according to DIN 43620,

(when SITOR semiconductor fuses are used,

a reduction of rated current is necessary,

see reference to technical information at start of chapter

)

Size 00 and

000

00 and

000

00 and

000

1 and 2 1 and 2 3 and 2 3 and 2

Conventional free-air thermal current

I

th

2)

A 63

125

160

250

400

630

800

Rated insulation voltage

U

i

V 690

1000

1000

1000

1000

1000

1000

Rated impulse withstand voltage

U

imp

kV 6

8

8

8

8

8

8

Rated operational voltage

U

e

50/60 Hz AC

V 690

DC

V 440 (3 conducting paths series-connected)

220 (2 conducting paths series-connected)

3)

Rated short-circuit making capacity with fuses

Peak value at 50/60 Hz 690 V AC

kA

220

220

220

176

176

105

105

Rated conditional short-circuit current with fuses

kA 100

100

100

80

80

50

50

At 50/60 Hz 690 V AC (rms value)

Max. rated current

I

n

of the fuses

A 80

160

160

400

400

630

4)

800

Max. permissible power loss of the installed fuse

• NH

W 6

9

11.5

32

45

48

62

• BS

W 8 (A2/A3) 11.5 (A4) 11.5

32

45

48

60.5

Permissible let-through current of the fuses

kA 8

17

17

30

5)

30

5)

50

50

Max. permissible let-through

I

2

t

value

kA

2

s 55

223

223

1000

1000

5400

10500

Breaking capacity

(infeed from the top or bottom)

At 400 V AC

• Breaking current

I

c

(at p.f. = 0.35, rms value)

A

500

1000

1280

2000

3200

5100

6400

• Rated operational current

I

e

with AC-21A, AC-22A, AC-23A

A 63

125

160

250

400

630

6)

800

6)

• Motor switching capacity AC-23A

kW 30

65

80

132

200

335

400

At 500 V AC

• Breaking current

I

c

(at p.f. = 0.35, rms value)

A

500

1000

1280

2000

3200

5100

6400

• Rated operational current

I

e

with AC-21A, AC-22A, AC-23A

A 63

125

160

250

400

630

6)

800

6)

• Motor switching capacity AC-23A

kW 40

90

110

185

280

425

500

At 690 V AC

• Breaking current

I

c

(at p.f. = 0.35, rms value)

A 500

1000

1280

2000

3200

5100

6400

• Rated operational current

I

e

with AC-21A, AC-22A, AC-23A

A 63

125

160

250

400

630

5)

800

5)

• Motor switching capacity AC-23A

kW 50

110

150

220

375

560

700

At 440 V DC (3 conducting paths series-connected)

7)

• Breaking current

I

c

(

L/R

= 15 ms)

A 250

500

640

1000

8)

1600

2520

9)

2520

9)

• Rated operational current

I

e

at DC-23A

A 63

125

160

250

10)

400

630

10)

630

10)

Rated short-time current

I

cw

(1 s current, rms value)

kA 2.5

3.2

3.2

8

11

32

32

Permissible ambient temperature

°C -25 ... +55 for operation

4)

,

°C -50 ... +80 when stored

Mechanical endurance,

operating cycles

15000 15000 15000 12000 12000 3000

3000

Degree of protection

IP00/IP20 (from the operator side, with fuse and terminal covers)

Power loss of the switch disconnector at

I

th

W 8.5

22

36

33

86

140

225

(plus power loss of the fuses)

Main conductor connections

Busbar systems, max. dimensions (W x T)

mm 25 x 9 45 x 10 45 x 10 40 x 12 40 x 15 40 x 17 40 x 17

Cable lug, max. conductor cross-section (stranded)

mm

2

35

70

120

150

2 x 150 or

1 x 240

2 x 240 2 x 240

Tightening torque

Nm 6 ... 7.5 7 ... 10 18 ... 22 35 ... 45 35 ... 45 56

56

Terminal screws

M6

M6

M8

M10

M10

M12

M12

Protective conductor connections

Flat bars

mm --

--

--

20 x 2.5 20 x 2.5 --

--

Cable lug, max. conductor cross-section (stranded)

mm

2

--

--

--

70

120

--

--