7

Switch Disconnectors

3VT Switch Disconnectors up to 1600 A

Introduction

7/45

Siemens LV 10 · 2014

Application

3VT switch disconnectors can be used as main control switches

for sub-distribution boards, repair and transfer switches for ca-

bles, busbars or unit combinations.

As three and four-pole versions, they ensure making and break-

ing of the specified rated current under load. At the same time,

they constitute a safety isolating function and isolating distance

in all low-voltage circuits.

The position of the operating toggle lever always matches that

of the contacts (positive operation).

All 3VT switch disconnectors meet the requirements of

IEC 60947-1 and IEC 60947-3.

Technical specifications

Rated current

I

n

A

160

250

630

1000

1600

Number of poles

3 and 4 3 and 4

3 and 4 3

3

Rated insulation voltage

U

i

V

690

Rated impulse withstand voltage

U

imp

kA

rms

/1s

2

3

7.5

15

20

Utilization category

• 690 V AC

AC-23A AC-23B

• 440 V DC

DC-22A DC-23B

Rated operational voltage

U

e

• 50/60 Hz AC

V

690

• DC

440 (3 conducting paths series-connected)

Rated short-time withstand current

I

cw

kA

rms

/1s

2

3

7.5

15

20

Rated impulse withstand voltage

U

imp

kV

8

Rated short-circuit making capacity

I

cm

/

U

e

• At 415 V AC

kA

2.8

4.26

12.5

30

40

• At 440 V DC

kA

2.8

4.26

12.5

30

40

Endurance

• Mechanical

Operating cycles 20 000

30 000

20 000

10 000

10 000

• Electrical

Operating cycles 6 000

3 000

5 000

4 000

4 000

Switching frequency

1/h

120

120

120

120

120

Power loss per pole

W

15

18

75

100

120

© Siemens AG 2014