Switch Disconnectors

5TE1 Switch Disconnectors up to 200 A

Introduction

7/27

Siemens LV 10 · 2014

7

Overview

The 5TE1 switch disconnectors are available from 100 A to

200 A in 3 and 4-pole versions and can be used as main control

switches, repair switches, outgoing feeder switches and emer-

gency mains switching off device.

The series corresponds to the requirements of IEC/EN 60947-3

and its key features are its compact and robust design, high

short-circuit strength, high DC breaking capacity and compre-

hensive accessories.

Its small footprint means it is easy to install in all types of

enclosures, distribution boards and control cabinets.

The devices are approved to UL 508 and KEMA certified.

Benefits

• Transparent enclosures ensure that the contact position is

always visible

• Contacts with double breaks ensure reliable insulation

characteristics

• Can be locked in the OFF position to allow for maintenance

work.

• With a red knob and yellow cap, it can also be used as an

emergency switching off device.

Technical specifications

5TE1.1 5TE1.2 5TE1.3 5TE1.4

Standards

IEC/EN 60947-3, UL 508

Approvals

UL508 for the following types: 5TE1320, 5TE1330,

5TE1340, 5TE1420, 5TE1430 and 5TE1440.

UL File No. E302554

Rated operational current

I

e

Per conduct. path At

U

e

= 400 V A

100

125

160

200

With utilization category AC-21A

415 V A

100

125

160

200

500 V A

100

125

160

200

690 V A

100

125

160

200

Rated operational current

I

e

Per conduct. path At

U

e

= 400 V A

100

125

160

200

With utilization category AC-22A

415 V A

100

125

160

200

500 V A

100

100

160

200

690 V A

63

63

160

200

Rated operational current

I

e

Per conduct. path At

U

e

= 400 V A

80

125

160

With utilization category AC-23A

415 V A

80

125

160

500 V A

50

125

125

690 V A

40

63

80

Rated operational current

I

e

2 poles in series

110 V A

100

160

With utilization category DC-23A

2 poles in series

220 V A

--

100

4 poles in series

220 V A

100

160

Rated operational voltage

U

e

V AC According to UL: 480, acc. to IEC: 690

Rated insulation voltage

U

i

V AC 690

Rated impulse withstand voltage

U

imp

2000 m

kV

8

Impulse test voltage

At sea level

kV

12.3

Max. rated operational power

At

U

e

= 400 V kW 44

69

88

With utilization category AC-23A

415 V kW 46

72

92

500 V kW 35

86

86

690 V kW 36

60

76

Rated thermal current

I

th

At 40 °C, 50 °C and 60 °C

A

100

125

160

200

Rated making capacity

At 415 V AC-23A

A

1875

3200

4000

Rated breaking capacity

At 415 V AC-23A

A

1000

1920

2400

Rated ultimate short-circuit breaking capacity

I

cm

Per conduct. path At

U

e

= 400 V kA 10

415 V kA 10

500 V kA

6.7

690 V kA

6.7

Rated short-time withstand current

I

cw

Per conduct. path

0.25 s kA

5

6

(peak value)

1 s

kA

2.5

3

Rated conditional short-circuit current

At

U

e

= 400 V kA 50

With back-up protection with back-up fuse

415 V kA 50

With identical rated current

500 V kA 50

690 V kA 33

33

20

18

Capacitive load

At 400 V

kVar

50

60

77

97

Number of poles

2/3/4

Rated power dissipation

P

v

Per pole

VA 2.9

4.5

6.5

10

Frequency

Hz

50/60

Conductor cross-sections

• Solid and stranded

mm

2

6 ... 50

--

• AWG cables

AWG 10 ... 1/0

8

• Copper busbars

mm

2

--

max. 20 × 6

Endurance

Electrical

Switch-

ing cy-

cles

1500

1000

Mechanical

20000

10000

Acc. to UL 508

I

n

A

--

80

100

125

UL 508 General Use 480 V

FLA (Full load amperes)

A

--

28

34

40

UL 508 Manual motor controller 230 V

Power

hp

--

10

25

30

UL 508 Manual motor controller 480 V

Power

hp

--

20

15

15

UL 508 short-circuit at 480 V

With Class H or K5 fuses

kA --

10

With J fuses

kA --

50