Switch Disconnectors

3NP5 Fuse Switch Disconnectors up to 630 A

Introduction

7/136

Siemens LV 10 · 2014

7

Technical specifications

1)

When observing degree of pollution 2 (instead of 3) operation is also possi-

ble up to

U

i

= 1000 V.

2)

Rated making and breaking current according to IEC 60947-3:

Rated making current

I

= 10 ×

I

e

(AC-23); 3 ×

I

e

(AC-22); 1.5 ×

I

e

(AC-21)

Rated breaking current

I

e

= 8 ×

I

e

(AC-23); 3 ×

I

e

(AC-22); 1.5 ×

I

e

(AC-21).

3)

When electronic fuse monitors are used, infeed must be from the top.

4)

When using isolating blades. If using fuse links, please observe specifica-

tions of fuse manufacturer.

5)

With busbar adapter.

6)

Values are valid when using LV HRC fuse systems with characteristic gG.

If using fuses for semiconductor protection, please refer to the assignment

table,

see page 7/145.

7)

When connecting one conductor.

For 2 conductors max. 1 x 50 mm

2

and 1 x 35mm

2

.

Standards

IEC 60947-1, IEC 60947-3, VDE 0660 Part 107

Type

3NP50

3NP52

3NP53

3NP54

Rated uninterrupted current

I

u

A

160

250

400

630

For fuse links acc. to IEC 60269-2

Size 00

1 and 0

2 and 1

3 and 2

Conventional free air thermal current

I

th

A

160

250

400

630

Rated operational voltage

U

e

• 50/60 Hz AC

V

690

• DC

V

440 (3 conducting paths series-connected), 220 (2 conducting

paths series-connected, with fuse monitoring through 3RV)

Rated insulation voltage

U

i

V

690

1)

690

1)

690

1)

690

1)

Rated impulse withstand voltage

U

imp

kV 6

6

6

6

Rated conditional short-circuit current

with fuses

(by fast switch on)

Rated current

Size/A 00/160

1/250

2/400

3/630

• At 500 V AC (rms value)

kA 50

50

50

50

Permissible let-through current of the fuses (peak value)

kA

15

25

40

50

Short-circuit strength with fuses

(with closed disconnector)

• Rated current

Size/A 00/160

1/250

2/400

3/630

• At 500 V AC (rms value)

kA

100

100

50

50

• Maximum permissible let-through

I

2

t

value

kA

2

s 223

780

2150

5400

• Permissible let-through current of the fuses (peak value)

kA

23

32

40

60

Rated short-circuit making capacity with isolating blades

2)

Size 00

1

2

3

• At 500 V AC (peak value)

kA

6

17

17

17

Rated making and breaking capacity

2)

(infeed from top or bottom)

3)

Size 00

1

0

2 1 3

2

Breaking current

I

c

• At p.f. = 0.35, rms value

A

1300

2500 1600 4000 2500 5040 4000

• At p.f. = 0.35, rms value

A

800

1280 1000 2520 1600 3200 2520

• At p.f. = 0.35 and 400 V AC, with fuse links, rms value

A

1600

2500 1600 4000 2500 5040 4000

Rated operational current

I

e

• At AC-21B, AC-22B, AC-23B at 500 V AC, with fuse links

A

160

250 160 400 250 630 400

• At AC-21B, AC-22B, AC-23B at 690 V AC, with fuse links

A

160

250 160 400 250 630 400

• At AC-21B, AC-22B

A

160

250 160 400 250 630 400

• At AC-23B

A

100

160 125 315 200 400 315

At 220 (440) V DC, with 2 (3) conducting paths series-connected and fuse links:

• Breaking current

I

c

(

L/R

= 15 ms)

A

640

1000 640 1600 1600 2520 1600

• Rated operational current

I

e

for DC-23B

A

160

250 160 250 250 630 400

Capacitor switching capacity

• Capacitor rating at 400 V AC

kvar

80

90

150

250

• Rated current

I

n

at 525 V AC

A

116

130

216

361

• Capacitor rating

kvar

100

125

200

300

• Rated current

I

n

A

110

137

220

330

Permissible ambient temperature

°C -25 ... +55 for operation

4

), -50 ... +80 during storage

Mechanical endurance,

operating cycles

1600

Degree of protection

• Without molded-plastic masking frame

IP00, for 3NP52 with terminal clamp connection,

degree of protection IP10

• With molded-plastic masking frame with closed fuse carrier on the operator side

IP30

• With molded-plastic masking frame with open fuse carrier

IP10

Power loss of the switch at

I

th

(without power loss of fuse links)

Without busbar adapter

W 7.8 (16.3)

5)

7.5

15

39

Maximum power loss of the usable fuses (per fuse)

6)

W 12

23

37

50

Main conductor connections

Flat terminal for connection of

• Crimped cable lugs acc. to DIN 46234 (conductor cross-section, stranded)

mm

2

2.5 ... 120 6 ... 150

6 ... 240

6 ... 2 × 240

• Pressed cable lugs acc. to DIN 46235 (conductor cross-section, stranded)

mm

2

16 ... 70 16 ... 150

16 ... 240

16 ... 2 × 240

• Busbars (usable busbar width)

mm 16 ... 22 22 ... 30

22 ... 30

22 ... 30

Clamp terminals

mm

2

2.5 ... 50

7)

35 ... 120

--

--

Auxiliary switch 1 NO + 1 NC (accessories)

The same voltage potential must be applied to the NO and NC

contacts

• At 50 Hz/60 Hz to 400 V AC, rated operational current

I

e

at AC-12/AC-15 A

A

16/6

• Flat plug-in terminals (DIN 46244)

A 6.3 ... 0.8

Permissible mounting positions

Vertical or horizontal installation

(switching capacity may be reduced with horizontal installation)

Signaling contact for solid-state fuse monitoring

2 NO + 1 NC

• Rated operational current

I

e

at 250 V, DC-13

A

0.27

• Rated operational current

I

e

at 240 V, AC-15

A

1.5

• Thermal free-air rated current

I

th

A

5