BETA Protecting
Miniature Circuit Breakers
Configuration
1/70
Siemens ET B1 · 10/2008
1
*
You can order this quantity or a multiple thereof.
Power loss for miniature circuit breakers according to UL and IEC, 5SJ4
Rated current
Characteristic B
Characteristic C
Characteristic D
I
n
R
i
P
v
R
i
P
v
R
i
P
v
A
m
W
m
W
m
W
0.3
--
--
12900
1.2
12600
1.1
0.5
--
--
4900
1.2
4600
1.2
1
--
--
1650
1.7
1480
1.5
1.6
--
--
620
1.6
570
1.5
2
--
--
440
1.8
435
1.8
3
--
--
197
1.8
190
1.7
4
--
--
115
1.8
100
1.6
5
--
--
115
2.9
100
2.5
6
85
3.1
74
2.7
73
2.6
8
--
--
40
2.6
39
2.5
10
16.5
1.7
13.5
1.4
11.9
1.2
13
11.7
2.0
10.2
1.7
10.2
1.7
15
8.5
1.9
7.8
1.8
7.7
1.7
16
8.5
2.2
7.8
2.0
7.7
2.0
20
6.7
2.7
5.5
2.2
5.5
2.2
25
4.3
2.7
4.2
2.6
4.2
2.6
30
3.4
3.1
3.5
3.2
3.0
2.7
32
3.4
3.5
3.5
3.6
3.0
3.1
35
2.8
3.4
2.8
3.4
2.7
3.3
40
2.8
4.5
2.8
4.5
2.5
4.0
45
2.8
5.7
2.7
5.5
2.5
5.1
50
2.1
5.3
2.1
5.0
2.0
5.0
60
1.7
6.1
1.7
6.1
1.7
6.1
63
1.7
6.7
1.7
6.7
1.7
6.7
© Siemens AG 2008