BETA Protecting

Miniature Circuit Breakers

Configuration

1/70

Siemens ET B1 · 10/2008

1

*

You can order this quantity or a multiple thereof.

Power loss for miniature circuit breakers according to UL and IEC, 5SJ4

Rated current

Characteristic B

Characteristic C

Characteristic D

I

n

R

i

P

v

R

i

P

v

R

i

P

v

A

m

W

m

W

m

W

0.3

--

--

12900

1.2

12600

1.1

0.5

--

--

4900

1.2

4600

1.2

1

--

--

1650

1.7

1480

1.5

1.6

--

--

620

1.6

570

1.5

2

--

--

440

1.8

435

1.8

3

--

--

197

1.8

190

1.7

4

--

--

115

1.8

100

1.6

5

--

--

115

2.9

100

2.5

6

85

3.1

74

2.7

73

2.6

8

--

--

40

2.6

39

2.5

10

16.5

1.7

13.5

1.4

11.9

1.2

13

11.7

2.0

10.2

1.7

10.2

1.7

15

8.5

1.9

7.8

1.8

7.7

1.7

16

8.5

2.2

7.8

2.0

7.7

2.0

20

6.7

2.7

5.5

2.2

5.5

2.2

25

4.3

2.7

4.2

2.6

4.2

2.6

30

3.4

3.1

3.5

3.2

3.0

2.7

32

3.4

3.5

3.5

3.6

3.0

3.1

35

2.8

3.4

2.8

3.4

2.7

3.3

40

2.8

4.5

2.8

4.5

2.5

4.0

45

2.8

5.7

2.7

5.5

2.5

5.1

50

2.1

5.3

2.1

5.0

2.0

5.0

60

1.7

6.1

1.7

6.1

1.7

6.1

63

1.7

6.7

1.7

6.7

1.7

6.7

© Siemens AG 2008