BETA Protecting

Overvoltage Protection Devices

Configuration

6/27

Siemens ET B1 · 10/2008

6

*

You can order this quantity or a multiple thereof.

Scope when installing overvoltage protection systems

The scope of IEC 60364-4-443 – Electrical installations of buildings,

Protection for safety; Protection against voltage disturbances

and electromagnetic disturbances – extends from the protective

device over the counter, through to the socket outlet.

The scope of IEC 61024-1 – Protection of structures against

lightning – and IEC 61312-1 – Protection against lightning

electromagnetic impulse – extends from the incoming main

feeder box through to the socket outlet and includes grounding

measures for SPDs.

If a lightning protection equipotential bonding is installed, it must

be connected to the base points of the overvoltage protective

devices.

TN-C system

TN-S system

TT system

PAS = Equipotential bonding strip

RCD (Residual Current Device): Residual current-operated circuit breakers

L1

L2

L3

N

PE

kWh

F3

F2

F2

F1

PEN

PAS

I2_13773a

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

TN system

Lightning

arrester

Plant grounding

Device protection

Lightning protection

equipotential bonding

L1

L2

L3

N

PE

kWh

F3

F2

F1

PEN

PAS

I2_13774a

F2

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

TN system

Lightning

arrester

Plant grounding

Device protection

Lightning protection

equipotential bonding

L1

L2

L3

N

PE

kWh

F3

F2

F1

PAS

I2_13775a

F2

RCD

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

S

P

D

Plant grounding

Device protection

Lightning arrester

TT system

Lightning protection

equipotential bonding

© Siemens AG 2008