3-pole
2/28
Siemens LV 10.1 · 2011
* You can order this quantity or a multiple thereof.
Type
Rated
current
I
n
Current setting of the
inverse-time delayed
overcurrent releases
"
L
"
I
R
Operating current of
the instantaneous
short-circuit releases
"
I
"
I
i
DT
I
cu
up to 55 kA at 415 V,
standard switching capacity N
see "Overview"
Order No.
Basic price
per PU
PU
(UNIT,
SET, M)
PS*/
P. unit
PG Weight
per PU
approx.
Order No. supplement
required,
see page 2/57
A
A
A
kg
3-pole, fixed-mounted, for motor protection,
63 A to 500 A, electronic releases LI
LCD-ETU40M, LI function
With thermal image, with adjustable trip class t
C
= 5, 10, 15, 20, 30, phase failure sensitivity adjustable in steps 5 ... 50 %
I
R
VL160/3VL2
63
25 ... 63
1.25 ... 11 ×
I
n
B
3VL27 06-1CP3
@
-....
1 1 unit 113 2.400
100
40 ... 100
1.25 ... 11 ×
I
n
B
3VL27 10-1CP3
@
-....
1 1 unit 113 2.400
160
64 ... 160
1.25 ... 11 ×
I
n
B
3VL27 16-1CP3
@
-....
1 1 unit 113 2.400
VL250/3VL3
200
80 ... 200
1.25 ... 11 ×
I
n
B
3VL37 20-1CP3
@
-....
1 1 unit 113 2.500
250
100 ... 250
1.25 ... 11 ×
I
n
B
3VL37 25-1CP3
@
-....
1 1 unit 113 2.500
VL400/3VL4
315
128 ... 315
1.25 ... 11 ×
I
n
B
3VL47 31-1CP36-....
1 1 unit 113 5.900
VL630/3VL5
500
250 ... 500
1.25 ... 11 ×
I
n
B
3VL57 50-1CP36-....
1 1 unit 113 9.300
N
I
L
NSE0_01419
CAT.A
25 CL
n
=250 A~
NSE-00547a
L3=179; N=0
L1=178; L2=181
ESC
>
Connection type can be selected by assignment of the 12th position of the Order No.
• Connection with box terminal
3
• Connection with screw terminal
6