3-pole
2/26
Siemens LV 10.1 · 2011
* You can order this quantity or a multiple thereof.
Communication:
• For accessories, see page 2/98.
• For more information see also chapters "Measuring Devices
and E-Counters" and "Software".
Type
Rated
current
I
n
Current setting of the
inverse-time delayed
overcurrent releases
"
L
"
I
R
Operating current of
the instantaneous
short-circuit releases
"
I
"
I
i
DT
I
cu
up to 55 kA at 415 V,
standard switching capacity N
see "Overview"
Order No.
For price
see page
2/32
PU
(UNIT,
SET, M)
PS*/
P. unit
PG Weight
per PU
approx.
Order No. supplement
required,
see page 2/57
A
A
A
kg
3-pole, fixed-mounted, for motor protection,
63 A to 500 A, electronic releases LI
ETU10M, LI function
With thermal image, with non-adjustable trip class t
C
= 10, with phase failure sensitivity 40 %
I
R
VL160/3VL2
63
25 ... 63
1.25 ... 11 ×
I
n
B
3VL27 06-1
@@
3
@
-....
1 1 unit 113 2.400
100
40 ... 100
1.25 ... 11 ×
I
n
B
3VL27 10-1
@@
3
@
-....
1 1 unit 113 2.400
160
64 ... 160
1.25 ... 11 ×
I
n
B
3VL27 16-1
@@
3
@
-....
1 1 unit 113 2.400
VL250/3VL3
200
80 ... 200
1.25 ... 11 ×
I
n
B
3VL37 20-1
@@
3
@
-....
1 1 unit 113 2.500
250
100 ... 250
1.25 ... 11 ×
I
n
B
3VL37 25-1
@@
3
@
-....
1 1 unit 113 2.500
VL400/3VL4
315
125 ... 315
1.25 ... 11 ×
I
n
B
3VL47 31-1
@@
36-....
1 1 unit 113 5.900
VL630/3VL5
500
200 ... 500
1.25 ... 12.5 ×
I
n
B
3VL57 50-1
@@
36-....
1 1 unit 113 9.300
ETU30M, LI function
With thermal image, with adjustable trip class t
C
= 10, 20, 30, with phase failure sensitivity 40 %
I
R
VL160/3VL2
63
25 ... 63
6/8/11 ×
I
n
B
3VL27 06-1
@@
3
@
-....
1 1 unit 113 2.400
100
40 ... 100
6/8/11 ×
I
n
B
3VL27 10-1
@@
3
@
-....
1 1 unit 113 2.400
160
64 ... 160
6/8/11 ×
I
n
B
3VL27 16-1
@@
3
@
-....
1 1 unit 113 2.400
VL250/3VL3
200
80 ... 200
6/8/11 ×
I
n
B
3VL37 20-1
@@
3
@
-....
1 1 unit 113 2.500
250
100 ... 250
6/8/11 ×
I
n
B
3VL37 25-1
@@
3
@
-....
1 1 unit 113 2.500
VL400/3VL4
315
125 ... 315
6/8/11 ×
I
n
B
3VL47 31-1
@@
36-....
1 1 unit 113 5.900
VL630/3VL5
500
200 ... 500
6/8/12.5 ×
I
n
B
3VL57 50-1
@@
36-....
1 1 unit 113 9.300
N
I
L
NSE0_00943
Alarm
Active
>1.05
X3
R
I
x
I
n
x
I
n
NSE0_02081
I
i
6
3
5 4
10
8
2
11
+
.5
.9
.8 .7
.4
.6
.4
.4 .4
.4
.07
.04
.06 .05
.08
.10
.09
.01
.03
.02
1.5
1.25
>
Connection type can be selected by assignment of the 12th position of the Order No.
• Connection with box terminal
3
• Connection with screw terminal
6
>
• Without communication preparation
SP
• With communication preparation
MP
I
L
NSE0_01419
Alarm
Active
>1.05
X3
R
I
x
I
n
NSE0_02082
+
I
i
I
i
I
n
I
n
I
i
I
n
20
10
=8x
=11x
10 30
20
20
Test
30
10
TC
30
=6x
.5
.9
.8 .7
.4
.6
.4
.4 .4
.4
.07
.04
.06 .05
.08
.10
.09
.01
.03
.02
>
Connection type can be selected by assignment of the 12th position of the Order No.
• Connection with box terminal
3
• Connection with screw terminal
6
>
• Without communication preparation
SS
• With communication preparation
MS
• Marine engineering-certified LRS, DNV and GL (not communication-ready)
LS
Z