3-pole
2/12
Siemens LV 10.1 · 2011
* You can order this quantity or a multiple thereof.
1)
Front busbar connection pieces are included in the scope of supply and
are to be fitted by the customer.
Communication:
• For accessories, see page 2/98.
• For more information see also chapters "Measuring Devices
and E-Counters" and "Software".
Type
Rated
current
I
n
Current setting of the
inverse-time delayed
overcurrent releases
"
L
"
I
R
Operating current of the
instantaneous
short-circuit releases "
I
"
I
i
DT
I
cu
up to 55 kA at 415 V, standard switching capacity N
See "Overview".
Order No.
Basic price
per PU
See also
page 2/32
PU
(UNIT,
SET, M)
PS*/
P. unit
PG Weight
per PU
approx.
Order No. supplement
required,
see page 2/57
A
A
A
kg
3-pole, fixed-mounted, for system protection, 50 A to 630 A,
thermal-magnetic releases LI
System protection, TM, LI function
With adjustable thermal overcurrent releases, adjustable short-circuit releases
VL160/
50
40 ... 50
300 ... 600
B
3VL27 05-1DC3
@
-....
1 1 unit 113 2.200
3VL2
63
50 ... 63
300 ... 600
B
3VL27 06-1DC3
@
-....
1 1 unit 113 2.200
80
63 ... 80
400 ... 800
B
3VL27 08-1DC3
@
-....
1 1 unit 113 2.200
100
80 ... 100
500 ... 1000
B
3VL27 10-1DC3
@
-....
1 1 unit 113 2.200
125
100 ... 125
625 ... 1250
B
3VL27 12-1DC3
@
-....
1 1 unit 113 2.200
160
125 ... 160
800 ... 1600
B
3VL27 16-1DC3
@
-....
1 1 unit 113 2.200
VL250/
200
160 ... 200
1000 ... 2000
B
3VL37 20-1DC3
@
-....
1 1 unit 113 2.300
3VL3
250
200 ... 250
1250 ... 2500
B
3VL37 25-1DC3
@
-....
1 1 unit 113 2.300
VL400/3VL4 200
160 ... 200
1000 ... 2000
B
3VL47 20-1DC36-....
1 1 unit 113 5.700
250
200 ... 250
1250 ... 2500
B
3VL47 25-1DC36-....
1 1 unit 113 5.700
315
250 ... 315
1575 ... 3150
B
3VL47 31-1DC36-....
1 1 unit 113 5.700
400
320 ... 400
2000 ... 4000
B
3VL47 40-1DC36-....
1 1 unit 113 5.700
VL630/3VL5 315
250 ... 315
1575 ... 3150
B
3VL57 31-1DC36-....
1 1 unit 113 9.000
400
320 ... 400
2000 ... 4000
B
3VL57 40-1DC36-....
1 1 unit 113 9.000
500
400 ... 500
2500 ... 5000
B
3VL57 50-1DC36-....
1 1 unit 113 9.000
630
500 ... 630
3150 ... 6300
B
3VL57 63-1DC36-....
1 1 unit 113 9.000
3-pole, fixed-mounted, for system protection, 63 A to 1600 A,
electronic releases LI
,
ETU10, LI function
With adjustable overcurrent releases, adjustable short-circuit releases
VL160/3VL2
63
25 ... 63
1.25 ... 11 ×
I
n
B
3VL27 06-1
@@
3
@
-....
1 1 unit 113 2.400
100
40 ... 100
1.25 ... 11 ×
I
n
B
3VL27 10-1
@@
3
@
-....
1 1 unit 113 2.400
160
64 ... 160
1.25 ... 11 ×
I
n
B
3VL27 16-1
@@
3
@
-....
1 1 unit 113 2.400
VL250/3VL3 200
80 ... 200
1.25 ... 11 ×
I
n
B
3VL37 20-1
@@
3
@
-....
1 1 unit 113 2.500
250
100 ... 250
1.25 ... 11 ×
I
n
B
3VL37 25-1
@@
3
@
-....
1 1 unit 113 2.500
VL400/3VL4 315
128 ... 315
1.25 ... 11 ×
I
n
B
3VL47 31-1
@@
36-....
1 1 unit 113 5.900
400
160 ... 400
1.25 ... 11 ×
I
n
B
3VL47 40-1
@@
36-....
1 1 unit 113 5.900
VL630/3VL5 630
525 ... 630
1.25 ... 10 ×
I
n
B
3VL57 63-1
@@
36-....
1 1 unit 113 9.300
VL800/3VL6 800
320 ... 800
1.25 ... 8 ×
I
n
B
3VL67 80-1
@@
36-....
1 1 unit 113 16.000
VL1250/3VL7 1000
400 ... 1000
1.25 ... 11 ×
I
n
B
3VL77 10-1
@@
36-....
1 1 unit 113 25.000
1250
500 ... 1250
1.25 ... 11 ×
I
n
B
3VL77 12-1
@@
36-....
1 1 unit 113 25.000
VL1600/3VL8
1)
1600
640 ... 1600
1.25 ... 9 ×
I
n
B
3VL87 16-1
@@
30-....
1 1 unit 113 31.300
N
L
I
NSE0_00691
5
6
7
nx
10
9
8
i
TM
50 C
CAT.A
=160A n
x n
.8
DC
R
1.0
16
I
I I
~=
NSE0_-00541a
I
I
iR
I
I
I
2
4
6
>
Connection type can be selected by assignment of the 12th position of the Order No.
• Connection with box terminal
3
• Connection with screw terminal
6
L
I
NSE0_00691
1.0
Alarm
Active
>1.05
X3
x
I
n
R
I
17
14
20
(S)
R
t
30
25
10
8
6
4
6
8
x
I
n
5 4
3
2
10
i
I
11
NSE0_02119
.5
.8
.7 .63
.9
.6
.45
.4
.95
2.5
1.25
1.5
>
Connection type can be selected by assignment of the 12th position of the Order No.
• Connection with box terminal
3
• Connection with screw terminal
6
>
• Without communication preparation
SB
• With communication preparation
MB
• Marine engineering-certified LRS, DNV and GL (not communication-ready)
LB
Z