Background Image
Table of Contents Table of Contents
Previous Page  354 / 543 Next Page
Information
Show Menu
Previous Page 354 / 543 Next Page
Page Background

18/24 IZM circuit-breakers, IN switch-disconnectors

Tripping characteristics IZMX16

2010 CA08103002Z-EN

www.eaton.com

IZMX16…U... Option Maintenance mode option +IZMX-DTU-ARMS

ARMS-maintenance mode

See Notes 2, 6, 11, 17, 18, 19, 20.

A Set values for overload protection I

r

B Maximum total opening delay

C Minimum total opening delay

D Set value for long delay t

r

E Set value non-delayed short-circuit protection I

i

F Set values for short-time delayed short-circuit protection with flat

characteristic curve

G The end of the characteristic curve is determined by the type of application

and the switching capacity of the selected switch.

H The characteristic curve for the overload release can extend up

to the M1 set value.

I

Available set values for non-delayed short-circuit protection I

sd

J Short-circuit release for very high currents

K Set values for short-time delay at I²t characteristic curve

L Set values for ground-fault protection

M Set values for ground-fault protection delay at

flat characteristic curve

N Flat characteristic curve for the delay time fault protection

O I

2

t characteristic for ground-fault protection delay time

1 The trip unit has a thermal memory, which can shorten the value in the

overload range. This function plays a role whenever a current is higher

than the overload release’s value and which is then isolated by a down-

stream circuit-breaker or the circuit-breaker itself. On a subsequent over-

load current the circuit-breaker will trip more quickly than normal. The

reduced value is inversely proportional to the time expired since the last

overload. After about five minutes the thermal memory is reset.

11 The listed overall switch-off times are conservative and take into account

the trip unit’s maximum response times, the circuit-breaker’s maximum

opening delays and the longest current interruption times with regard to

factors that contribute to worst-case conditions, such as maximum rated

operational voltage, single-phase interruptions and minimum power

factor. Fast breaking times are possible but depend on the system

conditions and the circuit-breaker model.

2 The end of the characteristic curve is determined by the type of

application and the switching capacity of the selected switch.

12 The ground-fault release is activated at a response value of

conventionally 100 % with a tolerance of ±10 %.

3 The overload release trips at 110 % I

r

with a tolerance of ±10 %

(indicated by the “Unit Status” LED). The short-time delayed short-circuit

release I

sd

is activated at a pick-up time of conventionally 100 % with

a tolerance of ±10 %.

13 Unless otherwise specified, the current value tolerances are ±10 % of the

values shown in the diagram.

4 When zone selectivity (ZSI) is activated in the short-time delayed short-

circuit release and no blocking signal is applied, the minimum time value

(0.10 s) applies irrespective of the short-time delay settings.

14 In combination with ARMS function, ground-fault protection is limited to

1200 A.

5 The upper lines of the I

2

t characteristic curves are horizontal from a value

of 8 × I

r

(indicated by the points).

15 When zone selectivity (ZSI) is activated in ground-fault protection and no

blocking signal is applied, the minimum time value (flat characteristic

curve) applies irrespective of the settings.

6 The listed overall switch-off times include the response times of the trip

unit, the opening times of the switch and the time required to switch off

the current.

16 The upper lines of the I

2

t characteristic curves are horizontal from a value

of 0.625 × I

r

(indicated by the points).

7 The characteristic curves apply to applications in a temperature range

from -20 °C to +55 °C. Temperatures over +85 °C cause automatic tripping,

indicated by an orange-colored LED. The circuit-breaker must be selected

according to the temperature-dependent derating values from the table in

the technical data.

17 The maintenance mode function (ARMS) must be activated with a switch

or through the communications terminals for these characteristic curves

to apply. A blue LED indicates that the maintenance mode settings are

active.

8 The non-delayed short-circuit release is activated at a response value of

conventionally 100 % with a tolerance of ±10 %.

18 The shown switch-off times apply for connection to an additional auxiliary

power supply.

9 The non-delayed short-circuit release can be disabled by the user with an

additional Off position.

19 Tripping by the ARMS Maintenance Mode Trip is indicated by the

non-delayed short-circuit protection LED.

10 All trip units feature an additional, permanently set non-delayed short-

circuit release, which becomes active at a peak value of 90 kA. Tripping

by this short-circuit release is indicated by a flashing INST LED. This

protective function remains active when non-delayed tripping is set to Off.

20 The tolerance is ±15 %.

1230DIA-101 (5722B22)

2 3 4 5 6 7 8 910

20

50 40 30

0.5 0.7 0.9

0.6 0.8 1

kA

t

[s]

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

4800A

g

15