MINDER PASSIVE INFRA RED SENSORS
l
The Minder is a multi-adjustable, passive infrared movement detector. People and animals radiate heat, which
is invisible to the human eye (infrared range). Consequently, the recorded infrared energy pattern changes when
they enter the detection zone
DETECTION RANGE DIAGRAMS
TECHNICAL DATA
l
Horizontal range
90
˚ 220˚ 280˚
of detection
Max. frontal range 12m 16m 16m
Max. bilateral range 6m 16m 10m
Water protection IP55 IP55 IP55
Switch off delay 1-3-5min 10 sec-30min 10 sec-30min
Dusk sensor, in Lux 3/15/Lux 0,5-300/Lux 0,5-300/Lux
Switching Capacity 3680 W/VA 3680 W/VA 3680 W/VA
Max switching Current 16AX 16AX 16AX
Operating Temperature -25˚C - +55˚C -25˚C - +55˚C -25˚C - +55˚C
MINDER FAULT FINDING ANALYSIS
l
NATURE OF FAULT
REASON FOR FAULT
REMEDY
Minder does not operate Lens covered or dirty Check power supply, uncover and/or clean lens
Inadvertent operation of Minder Hot air or smoke e.g. out of kitchens activate Minder Install Minder at a different location
Lamp is permanently on Permanent movement in the monitored area Make sure that no heat source is in the
detection zone and wait until adjusted time
lapse has run down.. For control purposes,
please cover the lens completely.
Minder is bridged to manual operation by Switch to automatic operation
additional switch
INSTALLATION
l
The Minder functions optimally when installed lateral to walking direction.
When selecting the installation site, ensure that:
●
The minder is not covered by rigid or moveable objects (e.g. roofing elements,
branches of tree, etc.).
●
When unit is installed above, or lateral to luminaires, a minimum distance is
always allowed between the unit and the luminaire, in order to prevent
maloperation.
●
when the unit is installed below luminaires, it is not heated up as a result of
radiant heat from the luminaire.
When mounted at a height of 2.5m, the detection range is as above mentioned,
though deviations in the mounting height cause changes in the detection range.
In the case of special conditions at the site (e.g. rows of trees, small plot of land,
proximity to road, etc.) the enclosed masking strip can be used to restrict the
detection range by sticking it on the Minder lens.
Standard Connection
With Break Switch
N
L
LS 16A
N L
N
L
LS 16A
N L
Rearfield detection
Additional protection for windows and doors up to the wall of the house,
even in case of installation directly above doors and windows, is provided
by the integrated rearfield detection.