Background Image
Table of Contents Table of Contents
Previous Page  27 / 91 Next Page
Information
Show Menu
Previous Page 27 / 91 Next Page
Page Background

OVERCURRENT RELEASE AND SWITCH

DISCONNECTOR MODULES

l

Rated Current (

I

n) Overcurrent adjustment (0.4 to 1x

I

n) LIST No

250A

100A .... 250A

7T325/OR3

400A

160A .... 400A

7T340/OR3

• Adjustable overcurrent release

• Adjustable short circuit release

400A

Switch Disconnector

7T363/SD

POWERSTAR 125

PANE LBOARDS & I NCOMI NG DEV I CE MODUL ES

27

17GG4012SW

7T340/OR3

17GG4012DC

DIMENSIONS 400A PANELBOARDS

l

LIST No Overall Height

Mod. Height (mm)

17GG4006SW

14 1064

17GG4008SW

15 1140

17GG4012SW

17 1292

17GG4016SW

19 1444

17GG4006DC

14 1064

17GG4008DC

15 1140

17GG4012DC

17 1292

17GG4016DC

19 1444

630

684 (9 Mod.)

188

400A PANELBOARD WITH TP SWITCHING UNIT

l

Outgoing Modular Height

ways Height (mm) LIST No

400A

6 14 1064

17GG4006SW

8 15 1140

17GG4008SW

12 17 1292

17GG4012SW

16 19 1444

17GG4016SW

• 400A rated Panelboards

• Busbar fault rated 25kA for 1 sec

• IP3X (door closed)

• Incoming terminations: 32mm wide lug connections*

• BSEN/IEC 61439-2: 2009

Designation of the incoming device is defined by the selection of an

overcurrent release or Switch Disconnector module.

THE SWITCHING UNIT MUST BE FITTED WITH ONE OF THESE MODULES.

* Dependant on the type of cable lug selected, cables up to 300mm

2

can be

connected to these 32mm wide connections

400A PANELBOARD WITH DIRECT CONNECTION

l

Inc. Terminals Outgoing Modular Height

only ways Height (mm) LIST No

400A

6 14 1064

17GG4006DC

8 15 1140

17GG4008DC

12 17 1292

17GG4012DC

16 19 1444

17GG4016DC

• 400A rated Panelboards

• Busbar fault rated 25kA for 1 sec

• IP3X (door closed)

• Incoming terminations: 30mm wide copper bar 1 x M10 connection

• BS EN/IEC 61439-2: 2009