Background Image
Table of Contents Table of Contents
Previous Page  9 / 36 Next Page
Information
Show Menu
Previous Page 9 / 36 Next Page
Page Background

9

FEATURES

• Easy to install and commission

• Shipped with typical default

values, decreasing commissioning

time

• Quick set mode allows basic

settings to be easily checked

and set

• Simple override switch

• Operates single or two

stage systems

• Standard 0 to 10Vdc output

• Night Set Back (NSB) and

set-up inputs

• Compatible with previously

installed Satchwell sensors

• Remote setting input

• Cost effective upgrade of obsolete

Climatronic controllers

Stand-alone

Controllers

PID 0-10Vdc Controller

Satchwell Product Catalogue – Stand-alone Controllers – PID 0-10Vdc Controller

CZT PID 0-10Vdc Controller

The CZT Controller is designed for use in systems such as room or return water

control. It can be used for single or two stage control and is suitable for use with

0 to 10Vdc actuators.

INSTALLATION DETAILS

Power supply:

230Vac (+10%, -6%)

50/60Hz

Power failure reserve:

Settings stored in

memory, 1 year battery for clock

Protection class:

IP 30

Switched Inputs

Night Set Back (NSB): Voltage free,

make/break contacts. Normally closed.

Set Up: remote voltage free, make/break

contacts. Normally closed.

Outputs

Control outputs: 2 x 0 to 10Vdc outputs

for heating and cooling.

Output Supply: 2 x 24Vac terminals used

to power the actuator(s) up to a total of

10VA maximum.

Control

Output

CZT 5305

Single or two stage

0 to 10Vdc for heating and cooling

Data Sheet 2.105

SensorS

Current Sensor

Type

Replaces

STR602

Space

DRT 3651

STR600

Space

DRT 3453

STR612

Space

DRT 3451

STD660

Duct

DDT 0001

STP660

Water (Immersion)

DWT 0001

STR602

Remote setting

RPW 4425

SVT 7-day Optimiser

This energy-saving controller can replace a conventional time switch on a heating

system and provides a variable start time dependent on the fall of room temperature

during the off period.

It is used to switch systems on and off and will substantially reduce energy

consumption compared with fixed time starting. In all but the very coldest weather

the start time is delayed until the latest time consistent with the amount of heat

necessary to reach the required temperature at occupancy time.

FEATURES

• Easy installation – only one

sensor required (packed with the

controller)

• Programme override switch

• Choice of day control by separate

compensator or built-in on/off day

control

• Minimum night ‘inside’

temperature protection

• Analogue and Digital clock

versions available

Version

Output relays

SVT 4201

Analogue clock

Plant, 250V, 2A (1A inductive)

Control, 250V, 2A (1A inductive)

SVT 4251

Digital clock

Data Sheet 2.001

INSTALLATION DETAILS

Power supply:

230V 50/60Hz

Power failure reserve:

For clock, 100 hours

Protection class:

IP 41

Associated Sensor:

STR614

(included with controller)

7-DAY OPTIMISER