Room reset controller

FEATURES

• Easy to install and commission

• Shipped with typical default

values, reducing commissioning

time

• Quick set mode allows basic

settings to be easily checked

and set

• Simple override switch

• Night Set Back (NSB), set-up,

summer and night sensor selection

switched inputs

• Optional night sensor to protect

heater battery from frost damage

• Up to 4 room sensors can be used

for average room temperature

• Remote setting input for room

set value

• Cost effective upgrade of obsolete

Climatronic controllers

• Compatible with previously

installed Satchwell sensors

Stand-alone

Controllers

Satchwell Product Catalogue – Stand-alone Controllers – Room reset controller

6

CXR

AHU Room Reset Controller

The CXR Controller is used to control room temperature by resetting the supply duct

air temperature. The room sensor resets the duct supply temperature to achieve

the desired room temperature. The room temperature can be sensed in the room or

extract duct. The supply duct loop has a purely proportional control action with the

room reset being a proportional plus integral control action.

Control

Output

CXR 5805

Single, two or three stage 24V actuator control

Data Sheet 2.110

INSTALLATION DETAILS

Power supply:

230Vac 50/60Hz

Power failure reserve:

settings stored in memory, 1 year battery for clock

Protection class:

IP 30

Switched Inputs

Night Set Back (NSB): remote voltage free, make/break contacts. Normally closed.

Set Up: Voltage free, make/break contacts. Normally closed.

Remote Low Limit (Summer): remote voltage free, make/break contacts.

Normally closed.

Night Sensor Selection: Voltage free, make/break contacts. Normally closed.

Outputs

Valve Actuator Output Triacs: 2 x 24Vac triacs, 1A

(0V switched and software interlocked).

Output Supply: 2 x 24Vac terminals used to power the actuator up to a total

of 10VA maximum.

SensorS

Current Sensor

Type

Replaces

STR602

Space

DRT 3651

STR600

Space

DRT 3453

STD660

Duct

DDT 0001

STP660

Water (Immersion)

DWT 0001

STC600

Water (Strap on)

DST 0001

STR602

Remote setting

RPW 4425