Background Image
Table of Contents Table of Contents
Previous Page  94 / 425 Next Page
Information
Show Menu
Previous Page 94 / 425 Next Page
Page Background

Full range of product

and technical information

place this part number

in a search engine and

download

2CDC110004C0206

1/86 control

ABB Low Voltage Industrial Products 0312

1

Relays and optocouplers

Optocouplers - R600

Optocoupler : 5 to 58 V DC output / 2 A - 6 mm .236’’ spacing

OB...OC 1000

OB...OC 1500

OB...OC 1000

5 V DC - 12 V DC

24 V DC 24 V AC/DC 48 V AC/DC 60 V AC/DC 115 V AC/DC 230 V AC/DC

50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz

5 mA

9 mA

5,4 mA

6,3 mA

4 mA

5,1 mA

4,2 mA

4 mA

4 V

12 V

15 V

27 V

27 V

50 V

80 V

15 μs / 250 μs

30 μs/400 μs

1 ms/7 ms

5 ms/20 ms 5 ms/20 ms 500 μs/10 ms 1 ms / 15 ms

2000 Hz

1000 Hz

60 Hz

20 Hz

20 Hz

50 Hz

35 Hz

1 mA

0,8 mA

0,9 mA

1 mA

1 mA

0,3 mA

0,3 mA

1 mA

2 A

< 50 μA

0,1 V

0,5 V

UL 94 V0

UL 94 V0

0,2 - 4 mm² / 24 - 12 AWG

0,2 - 2,5 mm² / 24 - 12 AWG

0,22 - 2,5 mm² / 24 - 12 AWG

0,22 - 2,5 mm² / 24 - 12 AWG

2,5 mm² / 12 AWG

2,5 mm² / 12 AWG

9 mm

.354"

9 mm

.354"

3,5 mm

.137"

3,5 mm

.137"

IP20

NEMA1

IP20

NEMA1

0,4 - 0,6 Nm

3.5 - 5.3 Ib.in

0,4 - 0,6 Nm

3.5 - 5.3 Ib.in

4,5 to 58 VDC

2500 V RMS

-40°C to +80°C

-20°C to +70°C (1)

Screw clamp

Spring clamp

, (pending) ,

, LRS ,

CEI 947-7-1 / CEI 947-1 / CEI 1131-2 (in relevant parts) / CEI 60664-1 / CEM : IRC 1000-4-2, 3, 4, 5, 6.

Characteristics

Opto. characteristics

INPUT

Input voltage +20% -15% on

DC, +10% -10% on AC

Frequency

Input current

Pull-in voltage at Is=100%

Switching time C / O

Operating frequency

Permissible leakage current

OUTPUT

Output voltage

Output current min.

Output current max.

Output leakage current at

Umax.

Residual voltage at I max and

U rated

typical

max.

Frequency on inductive load

Isolation Input / Output

TEMPERATURE

Ambient temperature storage

operating

Other characteristics

Body material

grey

Wire

Solid wire

size

Stranded wire

Rated wire size

Wire stripping length

Recommended screwdriver

Protection

Recommended torque

Approvals

Reference standards

(1) Over 55°C, blocks have to be mounted on horizontal rail with 10 mm spacing between each block. For vertical

rail mounting use temperature is 15°C less decreased.

Description

Type

Order Code

Price

Optocoupler module 2 A/DC

OBOC 1000-5-12VDC

1SNA645050R1700

25.88

OBOC 1000-24VDC

1SNA645051R0400

24.27

OBOC 1500-24VAC/DC

1SNA645025R2200

24.27

OBOC 1000-48-60VAC/DC

1SNA645053R0600

25.88

OBOC 1000-115VAC/DC

1SNA645026R2300

26.71

OBOC 1000-230VAC/DC

1SNA645026R2300

26.71

Accessories see page 1/80

OB...OC 1000 - 5-12 V DC

OB...OC 1500 - 24 V AC/DC

OB...OC 1000

24 V DC

48-60-115-230 V AC/DC

center of rail

Screw clamp module

DIN 3