Page Background

Full range of product

and technical information

place this part number

in a search engine and

download

2CDC110004C0206

1/71 control

ABB Low Voltage Industrial Products 0312

1

1)

• Temperature signal converter for thermo-

couples of the types K, J, T, S, E, N, R, B

• Continuously adjustable voltage signal input

0-10 mV and 0-50 mV

• Differential temperature meas. possible

1)

• Configurable output signal response on input

signal interruption (low fail safe / high fail safe)

• Adjustment and operating elements on the

front-side

• Short-circuit proof signal outputs

• Plug-in connecting terminals for inputs,

outputs and supply

Temperature signal converter for thermocouples

CC-U/TC and CC-U/TCR

CC-U/TC universal signal converter for thermocouples with 3-way electrical isolation

Wiring instruction

Type

Rated supply voltage

Order Code

Price

CC-U/TC

24-48 V DC

1SVR040004R0700

249.75

110-240 V AC

1SVR040005R0000

249.75

CC-U/TCR universal signal converter for thermocouples, with 2 threshold relay

outputs and 3-way electrical isolation

• Temperature signal converter for thermocouples of the types K, J, T, S

• 2 threshold relay outputs with one change-over contact each (threshold and respective hysteresis can be adjusted

independently from each other)

• Open-circuit or closed-circuit principle configurable by means of a DIP switch

• 2 yellow LEDs for clear status indication of the output relays

• Plug-in connecting terminals for inputs, outputs and supply

DIP switch settings

Wiring instruction

Type

Rated supply voltage

Order Code

Price

CC-U/TCR

24-48 V DC

1SVR040014R2000

194.21

110-240 V AC

1SVR040015R2100

194.21

1 2 43 5 6

-10...-2 V

-5...-1 V

-8...0 V

-4...0 V

0...1 mA

0...20 mA

4...20 mA

0...10 mA

0...800 μA

0...8 mA

0...400 μA

125...625 μA

166...833 μA

2...10 mA

100...500 μA

0...666 μA

0...16 mA

0...5 V

0...10 V

1...5 V

2...10 V

-10...+10 V

-5...+5 V

-10...0 V

-5...0 V

0...8 V

0...4 V

Switch 3

Output

1.25...6.25 V

0...6.66 V

-10...+3.33 V

-5...+1.66 V

-7.5...+2.5 V

-3.75...+1.25 V

1.66...8.33 V

-6.66...+6.66 V

-3.33...+3.33 V

0...0.5 mA

0...13.33 mA

2.5...12.5 mA

3.33...16.66 mA

0.2...1 mA

1 2 43 5 6 1 2 43 5 6

R

B

mV

N

K

J

T

S

E

0-100...900 °C

0-250...1350 °C

0-100...750 °C

0-100...400 °C

-150-0...400 °C

0-250...1550 °C

0-100...700 °C

0-200...1000 °C

0-100...650 °C

0-200...1300 °C

0-250...1350 °C

0-450...1700 °C

0-700...1750 °C

0-2...10 mV

0-10...50 mV

Type Range

Switch 1

Switch 2

Input

Low fail safe *)

High fail safe *)

DIP switch settings

1 2 43 5 6

S

J

K

T

0...240 °C

0...480 °C

0...1200 °C

0...250 °C

0...500 °C

0...1350 °C

-150...+120 °C

0...220 °C

0...400 °C

0...210 °C

0...380 °C

0...860 °C

0...1550 °C

Type Range

Switch

Input

Output

Closed-circuit principle

Open-circuit principle

OFF

Legend

no influence

ON

CC-U/TCR

2CDC 281 009 F0t03

Plug-in connecting

terminals

Threshold value for R1

Hysteresis for R1

Threshold value for R2

Hysteresis for R2

U: green LED -

supply voltage

R2: yellow LED -

Relay 2 energized

R1: yellow LED -

Relay 1 energized

Marker label

CC-U/STD

2CDC 281 002 F0t03

Plug-in terminals

Gain: Coarse adjustment

Gain: Fine adjustment

Offset adjustment

U: green LED -

supply voltage

Marker label

- /TC