Full range of product
and technical information
place this part number
in a search engine and
download
2CDC110004C0206
1/67 control
ABB Low Voltage Industrial Products 0312
1
Analog standard signal converter
CC-U/STD & CC-U/STDR
CC-U/STD universal signal converter with 3-way electrical isolation
• More than 120 configurations possible
• Configurable output signal response on input voltage signal interruption (low fail safe / high fail safe)
• Adjustment and operating elements on the front
• Short-circuit proof signal outputs
• Plug-in connecting terminals for inputs, outputs and supply
• Very fast signal transmission enables use in control systems
Wiring instruction
Type
Rated supply voltage
Order Code
Price
CC-U/STD
24-48 V DC
1SVR040000R1700
208.82
110-240 V AC
1SVR040001R0400
208.82
CC-U/STDR universal signal converter for standard signals, with 2 threshold relay outputs
and with 3-way electrical isolation
• Standard signal converter with 7 setting ranges
• 2 threshold relay outputs with one c/o contact each (threshold and respective hysteresis can be
adjusted independently from each other)
• Open-circuit or closed-circuit principle configurable by means of a DIP switch
• 2 yellow LEDs for clear status indication of the output relays
• Plug-in connecting terminals for inputs, outputs and supply
Wiring instruction
Type
Rated supply voltage
Order Code
Price
CC-U/STDR
24-48 V DC
1SVR040010R0000
171.75
110-240 V AC
1SVR040011R2500
171.75
DIP switch settings
DIP switch settings
CC-U/STD
2CDC 281 002 F0t03
Plug-in terminals
Gain: Coarse adjustment
Gain: Fine adjustment
Offset adjustment
U: green LED -
supply voltage
Marker label
*) Detectionof input voltage signal interruptions:
If the input signal circuit is interrupted, theoutput signal changes to the
adjustedminimum value (low fail safe)ormaximum value (high fail safe).
If "No fail safe" is configured, input signal interruptions arenotdetected.
4321
5
876
0...8V
0...20mA
4...20mA
10...50mA
20...4mA
20...0mA
0...50mV
0...100mV
0...250mV
0...500mV
0...1V
0...5V
-10...+10V
0...125mV
1...5V
0...10V
2... 10V
-11...+11V
10...0V
100...0mV
0...1mA
-55...+55mA
3...4
2...4
4...5
0...1
4...5
4...2
A...D
4...5
0...1
7...9
3...4
5...7
0
3...4
7...9
2
2...4
0
2
4...5
A...D
4...6
3
3
4
1
4
3
C
5
1
8
3
6
0
3
8
2
3
0
2
5
B
5
6
4
0
0
D
D
0
0
B...F
5...7
3...4
-
-
-
-
-
-
B...F
2CDC 282 019F0203
Switch1
Input
2.5...7.5V
3.33...9.99V
High fail safe *)
Gain Coarse
Type
Potentiometer
0...2.5V
-22.5...+22.5mV
-0.45...+0.45mA
Low faile safe *)
No fail safe *)
1 2 43 5 6
-10...-2V
-5...-1V
-8...0V
-4...0V
0...1mA
0...20mA
4...20mA
0...10mA
0...800 μA
0...8mA
0...400 μA
125...625 μA
166...833 μA
2...10mA
100...500 μA
0...666 μA
0...16mA
0...5V
0...10V
1...5V
2...10V
-10...+10V
-5...+5V
-10...0V
-5...0V
0...8V
0...4V
2CDC282 020F0203
Switch2
Output
1.25...6.25V
0...6.66V
-10...+3.33V
-5...+1.66V
-7.5...+2.5V
-3.75...+1.25V
1.66...8.33V
-6.66...+6.66V
-3.33...+3.33V
0...0.5mA
0...13.33mA
2.5...12.5mA
3.33...16.66mA
0.2...1mA
OFF
Legend
no influence
ON
CC-U/STDR
2CDC 281 003 F0t03
Plug-in connecting
terminals
Threshold value for R1
Hysteresis for R1
Threshold value for R2
Hysteresis for R2
U: green LED -
supply voltage
R2: yellow LED -
Relay 2 energized
R1: yellow LED -
Relay 1 energized
Marker label
OFF
Legend
no influence
ON
1 2 43 5 6
0...0 V
0...5 V
0...1 V
-10...+10 V
1...5 V
0...20 mA
4...20 mA
2CDC 282 005 F0204
Switch
Input
Output
Closed-circuit principle
Open-circuit principle