Appendix

Glossary

8/2

Siemens LV 36 · 2008

8

Rated operating voltage, (U

e

)

EN 60947-1; 4.3.1.1

Voltage fixed by the manufacturer. Several pertinent tests relate to its

determination, as may also the utilization category. Along with the

rated (operating) current, it determines the device’s utilization. The

highest value of rated operating voltage may in no case be greater

than the value of the rate insulation voltage U

i

.

Rated insulation voltage, (U

i

)

EN 60947-1; 4.3.1.2

Voltage measure to which are related tests of dielectric strength and

creepage distance.

Rated current, (I

n

)

EN 60947-2; 4.3.2.3

Current value of particular circuit breaker that can be handled uninter-

ruptedly. The highest current valued tripping the circuit breaker in

conformity with a specifically stated tripping characteristic.

Reduced rated current, (I

r

)

Specifically established, reduced value of

I

n

current for a regulated

time-dependent (thermal) release and that the circuit breaker can

handle continuously. Maximum setting is at value equal to

I

n

.

Changing

I

r

shifts the release’s tripping characteristic along the

current axis. (

I

r

= k x

I

n

holds where k

1)

Tripping time at a given I

r

multiple, (t

r

)

Time after which circuit breaker will trip, if a current flows through it that

is equal to the given multiple of

I

r

. Changing t

r

shifts the tripping

characteristic along the time axis.

Actuating current of (selective) release’s

time-independent delay, (I

ds

)

Minimum current value causing the release’s time-independent delay

to actuate.

Delay of time-independent delayed release, (t

v

)

If a current flows through the circuit breaker equal to at least

I

sd

but not

reaching

I

rm

the circuit breaker will trip with time delay t

v

. Total shut-off

time is influenced by the tripping of the circuit breaker itself and is

about 10 ÷ 20 ms longer.

Actuating current of time-independent

instantaneous, (I

rm

)

Minimum current value causing the time-independent instantaneous

release to actuate.

Rated operating current, (I

e

)

EN 60947-1; 4.3.2.3

Rated operating current of device (switch-disconnector) is fixed by the

manufacturer with consideration for the rated operating voltage, rated

frequency, rated operation, utilization category and type of protective

cover, if that comes into consideration.

Rated normal current, (I

u

)

EN 60947-1; 4.3.2.4

Current value set by the manufacturer and which the device can

handle in continuous operation, i.e. during a period longer than 8 hours

(weeks, months, or longer).

Rated ultimate short-circuit breaking capacity, (I

cu

)

EN 60947-2; 2.15.1; 4.3.5.2.1

Ultimate short-circuit breaking capacity value expressed as the rms

value of the alternating component of the assumed short-circuit current

that the circuit breaker must be able to manage in the mode: 1x swit-

ching off of the short circuit and a following 1x make-break sequence.

After testing, the circuit breaker need not be able to conduct the rated

current uninterruptedly.

I

cu

is set for the rated operating voltage at the

rated frequency and at the established power factor for alternating

current or at the time constant for direct current. Must fulfil the

condition:

I

cu

I

k

Rated short-circuit service breaking capacity, (I

cs

)

EN 60947-2; 2.15.2; 4.3.5.2.2

Value of the operating short-circuit breaking capacity expressed as the

rms value of the alternating component of the assumed short-circuit

current that the circuit breaker must be able to manage in the mode:

1x switching off of the short circuit and a following 2x make-break

sequence. May also be expressed as a percentage of

I

cu

. After

testing, the circuit breaker must be able uninterruptedly to conduct the

rated current and to switch off the overcurrent. Temperature increase

of the main terminals may be greater.

I

cs

is set for the rated operating

voltage at the rated frequency and at the established power factor for

alternating current or at the time constant for direct current. Permitted:

I

cs

I

k

Rated short-time withstand current, (I

cw

)

EN 60947-1; 4.3.6.1

EN 60947-2; 4.3.5.4

EN 60947-3; 4.3.6.1

Value of short-time withstand current specified by the manufacturer

that the device is able to handle without damage during a designated

time period (short-time delay). In case of alternating current, it is the

rms value of the alternating component of the assumed short-circuit

current