Background Image
Table of Contents Table of Contents
Previous Page  191 / 267 Next Page
Information
Show Menu
Previous Page 191 / 267 Next Page
Page Background

3VT4 Molded Case Circuit Breakers up to 1000 A

Circuit breakers, Switch disconnectors

5/5

Siemens LV 36 · 2008

5

Technical specifications

available,

-- unavailable

1) In case circuit breaker connection is reversed (input terminals 2, 4, 6 out-

put terminals 1, 3, 5),

I

cu

does not change.

Specifications

3VT4 circuit breakers

Switch disconnectors

Type

Standards

EN 60 947-2, IEC 947-2

EN 60 947-3, IEC 947-3

Approval marks

Number of poles

3

Rated current

I

n

A

315, 630, 800, 1000

--

Rated normal current

I

u

A

1000

Rated operational current

I

e

A

--

1000

Rated operational voltage U

e

V

AC max. 690

AC max. 690

DC max. 440

Rated frequency f

n

Hz

50/60

Rated impulse withstand voltage U

imp

kV 8

Rated insulation voltage U

i

V

690

Utilization category (selectivity) AC 690 V

A, B

--

Utilization category (switching mode)

AC 690 V

DC 440 V

--

--

AC-23 B

DC-23 B

Rated short-time withstand current U

e

=AC 690 V

I

cw

/t

15 kA/1 s

15 kA/1 s

Rated ultimate short-circuit breaking

capacity (rms value)

1)

I

cu

/U

e

AC 85 kA/230V

AC 65 kA/415V

AC 45 kA/500V

AC 20 kA/690V

--

Off-time at

I

cu

30 ms

--

Rated short-circuit service breaking

capacity (rms value)

I

cs

/U

e

AC 45 kA/230V

AC 36 kA/415V

AC 30 kA/500V

AC 20 kA/690V

--

Rated short-circuit making capacity

(peak value)

I

cm

/U

e

140 kA/AC 415 V

30 kA/AC 415 V

30 kA/DC 440 V

Losses per pole at

I

n

= 250 A

W 100

Mechanical endurance

cycles 10000

Electrical endurance (U

e

= AC 415 V )

cycles 4000

Switching frequency

cycles

/hr

120

Operating force

N 230

Front-side device protection

IP40

Terminal protection

IP20

Operating conditions

Reference ambient temperature

°C 40

Ambient temperature range

-40 ... +55

Working environment

dry and tropical climate

Degree of pollution

3

Max. elevation

m 2000

Seismic resistance

Hz

3g (8 ... 50)

Design modifications

Front/rear connection

/

Plug-in design

--

Withdrawable design

Accessories

Switches-auxiliary/relative/signal/early

/

/--/--

Shunt trip/with signal switch

Undervoltage release/with early switch with signal switch

/--

Manual front operating mechanism/lateral operating mechanism

right/left

/

Mechanical interlocking to the manual operating mechanism,

by Bowden wire

/

Motorized operating mechanism/with operations counter

/

Locking-type lever

Bolt sealing inset/additional cover for overcurrent release

/--