Background Image
Table of Contents Table of Contents
Previous Page  189 / 267 Next Page
Information
Show Menu
Previous Page 189 / 267 Next Page
Page Background

3VT4 Molded Case Circuit Breakers up to 1000 A

Circuit breakers, Switch disconnectors

5/3

Siemens LV 36 · 2008

5

Selection and ordering data

• The switching unit consits of:

- 3VT9 500-8CE30 phase barriers

- connecting sets for front connection - busbars connection

• The switching unit must be fitted with:

- overcurrent release ETU DP, MP and UP (circuit breaker) or

- 3VT9 410-6DT00 switch disconnector unit

- 3VT9 500-4WA40 withdrawable device

• The withdrawable device must be fitted with:

- 2 x 3VT9 500-4EF30 connection set (front connection) or

- 3VT9 500-4RD30 (rear connection)

• We recommend fitting the switching unit with:

- 3VT9 500-4SA40 mounting bolts set (4 x M8 x 60)

Accessories

Rated current

I

n

Switching capacity

I

cu

DT Order no.

PS*

Weight

per PU

approx.

A

kA

kg

Switching units

Fixed-mounted version, 3-pole

1000

65

B

3VT4 710-3AA30-0AA0

1 unit

23.000

Withdrawable design, 3-pole

1000

65

B

3VT4 710-3AA38-0AA0

1 unit

23.000

Withdrawable device

Withdrawbale device

B

3VT9 500-4WA40

1 unit

13.000

Rated current

I

n

Set current of the inverse-

time delayed overload trip

units „L“

I

r

DT Order no.

PS*

Weight

per PU

approx.

A

A

kg

ETU trip unit

System protection, ETU DP, LI function

• For protecting lines and transformers

315

125 ... 315

B

3VT9 431-6AC00

1 unit

0.500

630

250 ... 630

B

3VT9 463-6AC00

1 unit

0.500

800

315 ... 800

B

3VT9 480-6AC00

1 unit

0.500

1000

400 ... 1000

B

3VT9 410-6AC00

1 unit

0.586

Motor and generator protection, ETU MP, LI funktion

• Direct protection for motors and generators

• Suitable also for protecting lines and transformers

315

125 ... 315

B

3VT9 431-6AP00

1 unit

0.500

630

250 ... 630

B

3VT9 463-6AP00

1 unit

0.500

800

315 ... 800

B

3VT9 480-6AP00

1 unit

0.500

1000

400 ... 1000

B

3VT9 410-6AP00

1 unit

0.590

Universal protection, ETU UP, LSI function

• For protecting complicated loads or those not specified in advance

315

125 ... 315

B

3VT9 431-6AD00

1 unit

0.500

630

250 ... 630

B

3VT9 463-6AD00

1 unit

0.500

800

315 ... 800

B

3VT9 480-6AD00

1 unit

0.500

1000

400 ... 1000

B

3VT9 410-6AD00

1 unit

0.500

* You can order this quantity or a multiple thereof.