3VT3 Molded Case Circuit Breakers up to 630 A

Project planning aids

4/43

Siemens LV 36 · 2008

4

Dimensional drawings

Use of phase barriers and terminal covers for circuit

breakers and switch disconnectors

Fixed-mounted design

Front connection

• Terminals 1, 3, 5

- If U

e

= AC 415 V, it is necessary to use 3VT9 300-8CE30

phase barriers or 3VT9 300-8CB30 terminal covers

- For the connection of the main circuit to terminals 1, 3, 5, in-

sulated conductors, flexibars or rear connection terminals

are not used. It is necessary to use 3VT9 300-8CE30 phase

barriers or 3VT9 300-8CB30 terminal cover.

• Terminals 2, 4, 6

Only in case that the circuit breaker/switch disconnector is

connected to the the power supply using terminals 2, 4, 6 and

furthermore: if Ue AC 415 V, it is necessary to use 3VT9 300-

8CE30 phase barriers or a 3VT9 300-8CB30 terminal cover

- if insulated conductors are not used for connecting the main

circuit to terminals 2, 4, 6 , flexibars or rear connection are

not used, it is necessary to use 3VT9 300-8CE30 phase bar-

riers or 3VT9 300-8CB30 terminal cover.

Rear connection

• Neither phase barriers nor terminal covers need not be used.

Plug-in and withdrawable design

Neither phase barriers nor terminal covers need be used.

2 4 6

TEST

ON

OFF

2 4 6

TEST

ON

OFF

2 4 6

1 3 5

275

20

TEST

ON

OFF

B = 0

NSO0_00259

A

A1

D

A2

C = 0

1 3 5

1 3 5

B = 105 C = 80

B = 20

140

140

140

100 … 150

B = 20

3VT9 300-8CE30

1

1

1

A

minimum distance between the circuit breaker/switch-

disconnctor and uninsulated earthed wall (applicable for

connecting using insulated conductors, cables, flexibars

or with rear connection)

A1

minimum insulation length of bare conductors (using

3VT9 300-8CE30 phase barriers from 100 mm to max. 150

mm, or by adding additional insulation for the conductors

with barriers to obtain at least A1 value)

A2

minimum distance:

• between the circuit breaker/switch-disconnector and un-

insulated earthed wall (applicable for uninsulated con-

ductors and busbars)

• between the circuit breaker/switch-disconnector and

busbar

• between two circuit breaker/switch-disconnectors situat-

ed vertically above one another

• between uninsulated connections of two circuit break-

ers/switch-disconnectors above one another

B, C minimum distance between the circuit breaker/switch-dis-

connector and uninsulated earthed wall

D

minimum distance between uninsulated conductors