3VT3 Molded Case Circuit Breakers up to 630 A

Accessories and Components

Mounting accessories

Plug-in design

4/39

Siemens LV 36 · 2008

4

Recommended wiring of the circuit breaker in plug-in design

with motorized operating mechanism

Unplugging the circuit breaker

with motorized operating mechanism

• Each time before removing the circuit breaker, we recommend

turning first of all the AUTO/MANUAL switch on the motorized

operating mechanism to the MANUAL position

• More operating information can be found in the operating

instructions

• Not adhering to this procedure or failing to follow the recom-

mended wiring, could mean that the circuit breaker will not

successfully turn on at the first attempt.

Changes in states of switches when inserting and withdrawing the circuit breaker

0 = contact open, 1 = contact closed

1)

Accessory compartment 4, 5, 6 are for 4-pole version only.

L+

Q3

X4

YC

3

6

4

2

1

2

5

1

X3

MP

NC NO

S6

C

X3

12 10

11

M P

S

B

PE N-

NC

NO

S5

C

9 7

8

ON

OFF

NSO0_00350

Motor drive control circuits

Operating

counter

Motor drive

Symbol

Description

MP

3VT9 300-3M..0 motorized operating mechanism

M motor

P

storage device

X3

terminal strip to connect control circuits

X4

terminal strip for external operations counter

S5

switch indicating AUTO (NO-C)/MANUAL (NC-C) modes

S6

Switch to indicate full storage (ready to switch on: NO-C)

YC external operations counter 3VT9 300-3MF10

B

recommended wiring of the control circuits (control circuits not

included in motorized operating mechanism delivery)

ON make push button

OFF

break push button

S

switch to store up energy

Q3

motorized operating mechanism circuit breaker for

AC 24V LSN 4C/1

AC 48V LSN 4C/1

AC 110V LSN 4C/1

AC 230V LSN 2C/1

DC 24V LSN-DC 4C/1

DC 48V LSN-DC 4C/1

DC 110V LSN-DC 4C/1

DC 220V LSN-DC 2C/1

State of circuit breaker before removing

State of switches before removing

- inserted position

State of switches after removing -

withdrawn

Accessory compartment

1

2

3, 4, 5

(6 ... 9)

1)

1

2

3, 4, 5

(6 ... 9)

1)

Lever position of

the circuit breaker

State of the

main contacts

3VT9 300-2AC10

3VT9 300-2AH10

3VT9 300-2AC10

3VT9 300-2AH10

3VT9 300-2AC10

3VT9 300-2AH10

3VT9 300-2AC10

3VT9 300-2AH10

3VT9 300-2AC10

3VT9 300-2AH10

3VT9 300-2AC10

3VT9 300-2AH10

Switched on

1 1

0

0

1

1

0

1

0

1

0

0

1

Manually switched off or by motorized operating

mechanism

0 1

0

0

1

0

1

1

0

1

0

0

1

Switched off by releases

0 0

1

1

0

0

1

0

1

1

0

0

1

Switched off from switched-on state:

by means of auxiliary release, TEST push button

or by OFF push button on the motorized operat-

ing mechanism

0 1

0

1

0

0

1

1

0

1

0

0

1

4

3

3

-

2

1

4

3

3

-

2

1

4

3

3

-

2

1

4

3

2

1

4

3

3

-

2

1

4

3

2

1