Background Image
Table of Contents Table of Contents
Previous Page  132 / 267 Next Page
Information
Show Menu
Previous Page 132 / 267 Next Page
Page Background

3VT3 Molded Case Circuit Breakers up to 630 A

Circuit breakers · Switch disconnectors

4/12

Siemens LV 36 · 2008

4

Technical specifications

available,

-- unavailable,

+ in preparation

1)

In case circiut breaker connection is reversed (input terminals 2, 4, 6

output terminals 1, 3, 5),

I

cu

does not change.

Specifications

3VT3 763-2AA36/46/56-0AA0,

3VT3 763-3AA36/46/56-0AA0

Circuit breakers

Switch disconnectors

Type

Standards

EN 60 947-2, IEC 947-2

EN 60 947-3, IEC 947-3

Approval marks

Number of poles

3, 4

Rated current

I

n

A 250, 315, 400, 500, 630

--

Rated uninterrupted current

I

u

A 630

Rated operational current

I

e

A --

630

Rated operational voltage U

e

V

AC max. 690

AC max. 690

DC max. 440

Rated frequency f

n

Hz

50/60

Rated impulse withstand voltage U

imp

kV 8

Rated insulation voltage U

i

V

690

Utilization category

• selectivity AC 690 V

A

--

• switching mode AC 690 V

DC 440 V

--

--

AC-23 B

DC-23 B

Rated short-time withstand current U

e

= AC 690 V

I

cw

/t

8 kA/50 ms, 7 kA/300 ms, 6.5 kA/1 s

7,5 kA/5 s

Series U

e

3VT3 N

3VT3 H U

e

--

Rated ultimate short-circuit breaking

capacity (rms value)

1)

I

cu

60 kA

36 kA

20 kA

15 kA

100 kA

65 kA

35 kA

20 kA

AC 230 V

AC 415 V

AC 500 V

AC 690 V

--

Rated short-circuit breaking

capacity (rms value)

I

cs

/U

e

40 kA

18 kA

10 kA

8 kA

75 kA

36 kA

20 kA

15 kA

AC 230 V

AC 415 V

AC 500 V

AC 690 V

--

Rated short-circuit making capacity

(peak value)

I

cm

/U

e

75 kA/

140 kA

AC 415 V

14 kA/AC 415 V

14 kA/AC 440 V

Off-time at

I

cu

ms

10

--

Losses per pole at

I

n

= 250 A

W 75

Mechanical endurance

cycles 20000

Electrical endurance (U

e

= AC 415 V )

cycles 5000

Switching frequency

cycles/

hr

120

Operating force

N 110

Front-side device protection

IP40

Terminal protection

IP20

Operating conditions

Reference ambient temperature

°C 40

Ambient temperature range

°C -40 ... +55

Working environment

dry and tropical climate

Degree of pollution

3

Max. elevation

m 2000

Seismic resistance

Hz

3g ( 8 ... 50 )

Design modifications

Front/rear connection

/

Plug-in design

/+

Withdrawable design

/+

Accessories

Switches-auxiliary/relative/signal/leading

/

/

/

Shunt trip/with signal switch

Undervoltage release/with leading switch, with signal

switch

/

Front man. oper. mechanism/ lateral oper. mech. ri./left

/

Mechanical interlocking to the man.oper. mechanism,

by Bowden wire

/

Motorized oper. mechanism with operations counter

/

Locking-type lever

Bolt sealing insert/additional cover for overcurrent

release

/