3VT3 Molded Case Circuit Breakers up to 630 A

Circuit breakers · Switch disconnectors

4/11

Siemens LV 36 · 2008

4

Design

Installation and connection

Main circuit

• Is connected using Cu or Al busbars or cables, and possibly

cables with cable lugs

• For further connecting options, connecting sets can be used

(see page 4/9)

• Generally, conductors from the power supply are connected

to input terminals 1, 3, 5, (N) and conductors from the load to

terminals 2, 4, 6, (N). However, it is possible to reverse this

connection (exchanging input and output terminals) without

limiting the rated short-circuit ultimate breaking capacity

I

cu

)

• In case of feed-in from below, the circuit breakers/switch dis-

connectors must be fitted with 3VT9 300-8CE30 phase barri-

ers also on the side of terminals 2, 4, 6

• We recommend painting the connecting busbars in different

colors

• Input and output conductors/busbars must be mechanically

reinforced to avoid transmitting electrodynamic force to the

circuit breaker/switch disconnector during short-circuiting

• The way of connecting the main circuit must observe the

deionization space of the circuit breaker/switch disconnector

(see page 4/43)

.

Auxiliary circuits

• Auxiliary switches, shunt releases or undervoltage releases

are connected to the terminals using flexible 0.5 ... 1 mm

2

Cu

conductors.

• The motorized operating mechanism and auxiliary circuits of

the plug-in or withdrawable design are connected using a

connector.

Recommended cross-sections of cables, busbars and flexibars

for fixed-mounted, plug-in and withdrawable designs

Maximum circuit breaker/switch disconnector loads

in accordance with the ambient temperature

3VT3 circuit breaker/switch disconnector connection to pole

by 1 x 185 mm

2

Cu cable

Conductor cross-sections of main terminals

Rated current

I

n

Permissible cross-section

S

Dimensions of busbars

W x H

Cu

AI

Cu

Al

A

mm

2

mm

2

mm

mm

100

35

50

20 x 2

25 x 2

125

50

70

25 x 2

25 x 3

160

70

95

25 x 3

32 x 3

200

95

120

25 x 4

25 x 5

250

120

150

25 x 5

32 x 5

315

150

185

32 x 5

32 x 6

400

185

240

32 x 6

32 x 8

500

2 x120

2 x185

32 x 8

32 x 12

630

2 x185

2 x240

32 x 12

32 x 16

50°C

55 °C

60 °C

65 °C

70 °C

630 A

630 A

600 A

570 A

540 A

Order No.

Rated

current

I

n

Maximum permissible conductor cross-section S

Cable type

Sector-shaped

conductor, stranded

Sector-shaped

conductor, solid

Round conductor,

stranded

Round conductor,

solid

Busbars and

cable lugs

Technical infor-

mation

W x H

A

mm

2

mm

2

mm

2

mm

2

mm

Page

3VT9 300-4TA30

630

32 x...

3VT9 300-4TD00

3VT9 300-4RC30

630

32 x...

4/46, 4/57,

4/57, 4/57

3VT9 300-4RC00

3VT9 300-4TC30

400

35 ... 240 Cu

35 ... 240 Cu

35 ... 240 Cu

35 ... 240 Cu

--

3VT9 300-4TC00

3VT9 324-4TD30

400

150 ... 240 Cu/Al

120 ... 240 Cu/Al

150 ... 240 Cu/Al

120 ... 240 Cu/Al

3VT9 324-4TD00

3VT9 315-4TD30

315

25 ... 150 Cu/AI

16 ... 150 Cu/AI

25 ... 150 Cu/AI

16 ... 150 Cu/AI

3VT9 315-4TD00

3VT9 324-4TF30

630

2 x (150 ... 240) Cu/Al 2 x (120 ... 240) Cu/Al 2 x (25 ... 150) Cu/Al

2 x (120 ... 240) Cu/Al

4/45, 4/56

3VT9 324-4TF00

3VT9 315-4TF30

500

2 x (25 ... 150) Cu/Al

2 x (16 ... 150) Cu/Al

2 x (25 ... 150) Cu/Al

2 x (16 ... 150) Cu/Al

4/46, 4/57

3VT9 315-4TF00

3VT9 303-4TF30

250

6 x (6 ... 35) CuAl

6 x (6 ... 35) CuAl

6 x (6 ... 35) CuAl

6 x (6 ... 35) CuAl

4/46, 4/57

3VT9 303-4TF00

3VT9 300-4ED30

400

4/47

3VT9 300-4EE30

630

4/47

3VT9 300-4TN30

10/16

1.5 ... 2.54 ... 6 flexible conductor