Total Solution to Earthing & Lightning Protection |
9AKK106354A3360
4/9
4
Product selection guide - Free-standing air termination
Rod height
Interception pole Frame (where required) and base part no. for windspeeds
(m)
Part no.
< 130 km/h
< 150 km/h
< 170 km/h
< 190 km/h
0.5
RA215 or RA015 103101-FU
103101-FU
103101-FU
103101-FU
1
RA225 or RA025 103101-FU
103101-FU
103101-FU
103101-FU
1.5
RA230 or RA030 103110-FU
103110-FU
103110-FU
103110-FU
2
RA240 or RA040 103110-FU
103110-FU
103110-FU
103110-FU
3
912000-FU
499000-FU / 4 x 499100-FU
499000-FU / 4 x 499100-FU
499000-FU / 4 x 499100-FU
499000-FU / 4 x 499100-FU
3.5
912001-FU
499000-FU / 4 x 499100-FU
499000-FU / 4 x 499100-FU
499000-FU / 4 x 499101-FU
499000-FU / 4 x 499101-FU
4
912002-FU
499000-FU / 4 x 499100-FU
499000-FU / 4 x 499101-FU
499000-FU / 8 x 499100-FU
499000-FU / 8 x 499101-FU
4.5
912003-FU
499005-FU / 3 x 103101-FU
499005-FU / 3 x 103110-FU
499005-FU / 3 x 103118-FU
499006-FU / 3 x 103103-FU
5
912004-FU
499005-FU / 3 x 103101-FU
499005-FU / 3 x 103110-FU
499005-FU / 3 x 103118-FU
499006-FU / 3 x 103103-FU
5.5
912005-FU
499005-FU / 3 x 103110-FU
499005-FU / 3 x 103118-FU
499006-FU / 6 x 103103-FU
499006-FU / 3 x 103103-FU
6
912006-FU
499006-FU / 6 x 103103-FU
499006-FU / 6 x 103103-FU
499006-FU / 6 x 103103-FU
499006-FU / 6 x 103101-FU
6.5
912007-FU
499006-FU / 6 x 103103-FU
499006-FU / 6 x 103103-FU
499006-FU / 6 x 103101-FU
499006-FU / 6 x 103118-FU
7
912008-FU
499006-FU / 6 x 103103-FU
499006-FU / 6 x 103101-FU
499006-FU / 6 x 103110-FU
On request
7.5
912009-FU
499006-FU / 6 x 103101-FU
499006-FU / 6 x 103110-FU
499006-FU / 6 x 103118-FU
On request
8
912010-FU
499006-FU / 6 x 103110-FU
499006-FU / 6 x 103118-FU
499007-FU / 10 x 103118-FU
On request
9
912011-FU
499007-FU / 10 x 103118-FU
499007-FU / 10 x 103118-FU
499007-FU / 10 x 103118-FU
On request
10
912013-FU
499007-FU / 10 x 103118-FU
499007-FU / 10 x 103118-FU
On request
On request
Product selection
Free-standing air rod selection is based on two factors:
–– Air rod height required to create the necessary protective
zone around the equipment
–– Anticipated wind loading at the installation
Wind loading is an important factor, especially for taller
interception air rods as extreme weather can subject them to
fatigue mechanisms.
For UK installations, the map featured right highlights four key
wind zones from which the appropriate free-standing air rod
can be established.
Relevant part numbers can then be determined through cross
referencing wind loading with the height of air rod required
in the table below.
For non-UK installations, please refer to available data for
local wind conditions or contact your Furse representative to
discuss your particular requirements.
Liverpool
Manchester
Sheffield
Kingston-upon-Hull
Stoke-on-Trent
Birmingham
Aberystwyth
Swansea
Newport
Oxford
Bristol
Brighton
Plymouth
London
Norwich
Ipswich
Shetland
Islands
Orkney
Islands
Thurso
Inverness
Aberdeen
Fort William
Dundee
Glasgow Edinburgh
Newcastle
York
Leeds
Outer
Hebrides
Liverpool
Manchester
Sheffield
Kingston-upon-Hull
Stoke-on-Trent
Birmingham
Aberystwyth
Swansea
Newport
Oxford
Bristol
Brighton
Plymouth
London
Norwich
Ipswich
Shetland
Islands
Orkney
Islands
Thurso
Inverness
Aberdeen
Fort William
Dundee
Glasgow Edinburgh
Newcastle
York
Leeds
Outer
Hebrides
Key
–– Zone 1
n
Windspeed:
< 130 km/h
–– Zone 2
n
Windspeed:
< 150 km/h
–– Zone 3
n
Windspeed:
< 170 km/h
–– Zone 4
n
Windspeed:
< 190 km/h
UK wind zone map