Background Image
Table of Contents Table of Contents
Previous Page  291 / 300 Next Page
Information
Show Menu
Previous Page 291 / 300 Next Page
Page Background

Furse, Wilford Road, Nottingham, NG2 1EB • Tel: +44 (0)115 964 3700 • Email:

enquiry@furse.com

• Web:

www.furse.com

Lightning protection of hazardous areas

TSC-0912 - 09.10.12

Lightning protection of hazardous

areas in line with ATEX/IECEx

With hazardous areas at risk from the consequences

of direct and indirect lightning, a comprehensive

approach to lightning protection in line with

BS EN/IEC 62305 should be considered.

This should cover structural lightning protection,

earthing & equipotential bonding, and transient

overvoltage protection.

The zonal approach to lightning protection, as

established in BS EN/IEC 62305 (see page 272,

Lightning Protection Zones), is applicable for designing

an LPS suitable for hazardous areas, considering the

following points.

Structural lightning protection

For locations with potentially explosive atmospheres,

as defined by BS EN/IEC 62305:2011 the appropriate

Class of LPS required shall be dictated by the risk

assessment process in BS EN/IEC 62305-2.

An isolated LPS is required since the structure includes

combustible materials and/or presents a risk of

explosion, with minimum separation distances adhered

to between the LPS and structural metallic parts to

remove any risk of sparking.

Additionally, catenary conductors raised high above

the structure should be considered, where these are to

protect locations where combustibles are present, such

as gas/oil storage tanks.

Earthing & equipotential bonding

The earth termination system should meet the

requirements set out in BS EN/IEC 62305-3 - a single,

integrated earth termination system combining

lightning protection, power and telecommunications

systems. It should provide low electrical resistance (less

than 10 Ohms) and be appropriately bonded to ensure

no metallic part is at a different potential with respect

to another.

Where incoming or outgoing services cannot be

bonded directly to earth, these should be protected by

a suitable SPD.

Following the zonal approach in BS EN/IEC 62305,

services passing from LPZ 0 to LPZ 1 should be

protected against partial lightning currents using a

lightning current/equipotential bonding SPD (tested to

10/350 µs waveform), as well as transient overvoltages

(SPD tested to 8/20 µs waveform).

Electronic systems protection

Electrical and electronic equipment/systems need to be

protected against transient overvoltages, since damage

to components could lead to risk of sparks or fire.

Equipment/systems sited in a safe area which do not

contribute to safety in a potentially explosive

atmosphere can be protected against transient

overvoltages using appropriate standard SPDs, as

defined by BS EN/IEC 62305.

However, equipment/systems sited in potentially

explosive atmospheres (Zone 1, 2) or contributing to

safety within these atmospheres require an SPD

suitably tested and approved by ATEX.

All SPDs installed on site should form a coordinated

set to ensure protection levels are maintained and

effective throughout.

Protection of intrinsically safe (IS) circuits

Intrinsic Safety (IS) is a concept for protecting

hazardous areas from dangerous sparking, whereby

sparks from electrical equipment and circuitry are

prevented through the use of IS barriers.

These barriers limit the available electrical energy that

could cause an explosion to below ignition threshold.

IS Barriers however are not surge protectors but are

field instruments which are themselves at risk from

transient overvoltages. IS circuits therefore need to be

protected from transient overvoltages by a suitable

(ATEX approved) SPD.

Protection should be applied at the boundary between

the hazardous and non-hazardous area (see Figure 23),

with an isolated screen SPD installed within the

hazardous area (Zone 1, 2).

For more information on protecting hazardous area

installations from lightning, please contact us.

Instrumentation

Instrument

Earth

ESP SL30X/I

ESP SL30X

Control cabinet

IP54

enclosure

Instrument

Earth

System

Earth

Field

earth

Open end cable screen

ZONE 0

Hazardous Area Zones 1, 2

Non-Hazardous Area

Isolated

coupling

IS

Barrier

ZONE 1

ZONE 2

Figure 23: The installed SPD

(here the ESP SL30X Series)

provides protection for the

instrumentation as well as

providing protection for

the IS Barrier.

The isolated screen version

(ESP SL30X/I) should be

used in Zone 1, 2.