The IP and IK degrees of protection provided by an enclosure must be specified as

a function of the various external influences defined by standard IEC 30364-5-51,

in particular:

b

b

presence of foreign solid bodies (code AE)

b

b

presence of water (code AD)

b

b

mechanical stress (code not specified)

b

b

capability of persons (code BA)

b

b

...

Prisma switchboards are designed for indoor installation.

Unless the rules, standards and regulations of a specific country stipulate otherwise,

Schneider Electric recommends the following IP and IK values based on French

guide UTE C 15-103 (March 2004).

Using the table

1

Opposite the relevant premises, read the recommended IP and IK values.

2

The

b

symbol indicates the enclosure or cubicle satisfying the criteria of the UTE

guide.

Any enclosure or cubicle with a higher degree of protection can also be used.

3

If several degrees of protection are possible (refer to the standard for more

details) and the

v

and

b

symbols are indicated (e.g. 24

v

/25

b

), enclosures that

correspond to the higher degree of protection (

b

) are suitable for the lower

degree of protection (

v

).

Example:

Selection of an enclosure for a laundry room.

Minimum degree of protection: IP21/IK02

Awall-mounted enclosure with a door (plain or transparent), a canopy and a gasket

offer IP43/IK08 degrees of protection and are therefore suitable for this application.

Type of premises

Enclosures

Wall-mounted

enclosure

without door

with door

with door + canopy with door + canopy +

gasket

IP55

Floor-standing

enclosure

without door

with door

with door + canopy with door + canopy+

gasket

Min. IP/IK

required

IP30/IK07

IP30/IK08

IP31/IK08

IP43/IK08

IP55/IK10

IP IK

Domestic or comparable premises or locations

Porch

24

07

b

b

Bathrooms (see washrooms)

Bicycles, motorcycles, tricycles, etc.

(premises for)

20

07

b

b

Water, sewer and heating

connections

23

02

b

b

Laundries

21

02

b

b

Cellars, garages, furnace rooms

20

02/07 b

b

Bedrooms

20

02

b

b

Trash rooms

25

07

b

b

Halls in cellars

20

07

Courtyards

24/25 02/07

b

b

Kitchens

20

02

b

b

Shower rooms (see washrooms)

Indoor stairways and alleys

20

02/07 b

b

Outdoor stairways and outdoor

alleys without roofs

24

07

Outdoor alleys with roofs

21

02

b

b

Attics (roof space)

20

02

b

b

Garden shelters

24/25 02/07

b

b

Latrines

20

02

b

b

Dustbin rooms

25

02/07

b

b

Ironing room

20

02

b

b

Access ramps to garages

25

07

b

b

N/A

Additional information

Enclosure characteristics

Selectionof enclosures

according to thepremises