A-58

The Masterpact Earthing Switch can be racked into any

compatible Masterpact NW chassis in place of a

Masterpact circuit breaker. It is used to interconnect

and earth the phase and neutral conductors of an

electrical installation to ensure the safety of personnel

during servicing. It can be locked in earthed position.

Main characteristics

Rated insulation voltage

Rated operational voltage

Rated current

Latching capacity

Rated short-time withstand

current

1000 V

690 V

800 to 4000 A

135 kA peak

60 kA/1s

50 kA/3s

Compatibility

Compatible with drawout NW08 to NW40 circuit breakers, types

N1/H1/NA/HA, 3-pole and 4-pole rear connected versions

Remote indication

12 ON/OFF indication contacts that can be used according to

the chassis auxiliary wiring

PB104426A50

The Earthing Switch is compatible with Masterpact NW08 to NW40 type N1, H1,

NA and HA circuit breakers in both 3-pole and 4-pole versions. It has two parts:

a chassis earthing kit for installation on the Masterpact NW chassis. Two different

b

b

versions are available for 3-pole and 4-pole chassis.

the Earthing Switch itself, which is a specific Masterpact NW device that can be

b

b

racked into any chassis equipped with an earthing kit, in place of the circuit breaker.

Two versions are available (3-pole and 4-pole).

An earthing kit must be installed on the chassis of each circuit breaker protecting a

circuit that may require earthing while work is being carried out. However, a single

earthing switch is often sufficient for an entire installation if only one circuit is to be

serviced at any given time.

The standard Earthing Switch comes with the short-circuit bar installed across the

bottom (downstream) connections for earthing of the upstream portion of the circuit.

The user can easily move the short-circuit bar to the top connections if the

downstream portion of the circuit needs to be earthed.

Earthing kit

(for chassis)

Earthing switch

(front view)

DB125557

DB125558

Earthing switch

(rear view)

DB125559

DB125560

With short-circuit bar on the top connections.

With short-circuit bar on the bottom connections.

DB125561

Locking in earthed position by 3 padlocks

The standard Earthing Switch can be locked in earthed position by one to

three padlocks as long as the following conditions are satisfied:

the Earthing Switch must be in "connected" position in a chassis equipped with an

b

b

earthing kit

the Earthing Switch must be in “ON” position.

b

b

Under these conditions, the installation is earthed.

When the Earthing Switch is locked in earthed position:

it cannot be moved to "disconnected" position (a shutter prevents insertion of the

b

b

racking handle)

it cannot be turned "OFF" (a shutter prevents access to the "OFF" pushbutton).

b

b

Earthing switch Masterpact

Functions

and characteristics

version: 1.2

207E2510.indd