A-46

Source-changeover systems

Electrical interlocking

Electrical interlocking is carried out by an electrical control device.

For Compact NS630b to 1600, this function can be implemented in one of two ways:

using the IVE unit

b

by an electrician in accordance with the chapter "Electrical Diagrams" of the

b

catalogue source-changeover system.

Characteristics of the IVE unit

external connection terminal block:

b

inputs: circuit breaker control signals

v

outputs: status of the SDE contacts on the “Normal” and “Replacement” source

v

circuit breakers

2 connectors for the two “Normal” and “Replacement” source circuit breakers:

b

inputs:

v

- status of the OF contacts on each circuit breaker (ON or OFF)

- status of the SDE contacts on the “Normal” and “Replacement” source circuit

breakers

outputs: power supply for operating mechanisms

v

control voltage:

b

24 to 250 V DC

v

48 to 415 V 50/60 Hz - 440 V 60 Hz.

v

The IVE unit control voltage must be same as that of the circuit breaker operating

mechanisms.

Electrical interlocking is used with a mechanical

interlocking system.

An automatic controller may be added to take into

account information from the distribution system.

Moreover, the relays controlling the “normal”

and “replacement” circuit breakers must be

mechanically and/or electrically interlocked to

prevent them from giving simultaneous

closing commands.

Necessary equipment

For Compact NS630b to 1600, each circuit breaker must be equipped with:

a motor mechanism

b

an available OF contact

b

a CE connected-position contact (carriage switch) on withdrawable circuit

b

breakers

an SDE contact.

b

DB128058

IVE unit.

DB110903

Standard configuration for Compact NS

Types of mechanical interlocking

Possible combinations Typical electrical diagrams

Diagram no.

2 devices

QN

QR

Compact NS630b to 1600:

0

0

b

electrical interlocking with lockout after fault:

1

0

v

permanent replacement source (without IVE)

51201180

0

1

v

with EPO by MX (without IVE)

51201181

v

with EPO by MN (without IVE)

51201182

v

permanent replacement source (with IVE)

51201183

v

with EPO by MX (with IVE)

51201184

v

with EPO by MN (with IVE)

51201185

b

automatic control without lockout after fault:

v

permanent replacement source (without IVE)

51201186

Functions and characteristics