1/25
Technical
Section 9
Dimensions
Section 10
C60 Vigi modules
Instantaneous 10 to 1000mA
Selective
s
: 300mA and 1000mA
Earth leakage
protection
Possible combinations
Vigi C60
y
25 A Vigi C60
y
40 A Vigi C60
y
63 A
C60 < 25 A
n
n
n
C60 < 40 A
-
n
n
C60 < 63 A
-
-
n
Note
: guaranteed by foolproof mechanical mounting
Combined C60 circuit breaker + C60 Vigi module:
b
b
Non-locking installation (disassembly possible) (fig. 1)
v
v
Mounting with locking (disassembly possible but with visible trace of disassembly
v
v
as per appendix G of standard EN 61009-1) (fig. 2)
Disassembly after locking, visible trace of disassembly by breaking the lock as per
v
v
appendix G of standard EN 61009-1 (fig. 5)
Hinged captive screw shield that can be sealed with a wire, used for checking and
b
b
retightening the connection terminals if required (fig. 3-4)
Technical data
Voltage rating
130 V AC ±10 %
230...400 V AC ±10 %
Current rating
l
n
y
25 A, l
n
y
40 A and l
n
y
63 A
Operating frequency
AC type: 50/60 Hz
A, A si, A SiE types: 50 Hz
Trip unit, instantaneous or selective Fixed sensitivities for all ratings
Test button: minimum operating voltage
at 50 Hz
Vigi C60 130 V: 105 V
Vigi C60 230/400 V:
- 10/30/100/300 mA: 189 V
- 500/1000 mA: 193 V
Manual control , by means of a handle
providing two reset modes for the C60
circuit breaker + C60 Vigi module
assembly
Either with a single action
Or separately
The C60 Vigi module resets before the
circuit breaker
Mechanical indication
Indication of the earth fault on the front face
by a red mechanical indicator on the C60
Vigi module operating handle.
Electrical indication
By the SD indicating auxiliary switch
(supplied separately)
Operating temperature
AC type: -5 °C to +60 °C
A, A si, A SiE types: -25 °C to +60 °C
Storage temperature
-40 °C to +70 °C
Connection by tunnel
terminals
Flexible 16 mm
2
cables or rigid 25 mm
2
cables for C60 Vigi modules with ratings
y
25 A
Flexible 25 mm
2
cables or rigid 35 mm
2
cables for C60 Vigi modules with ratings
y
40 A or
y
63 A.
Weight (g)
Type
2P
3P
4P
Vigi
y
25 A 120
180
180
Vigi
y
40 A 120
180
180
Vigi
y
63 A 150
210
210
Accessories
Screw shield: prevents all contact with the C60 Vigi module output terminal screws
b
b
Spare lock: to replace the lock, after removing a C60 Vigi module previously
b
b
secured to a C60 circuit breaker