1/24
Technical
Section 9
Dimensions
Section 10
1
Function
They are used with C60 2P, and 4P circuit breakers to provide:
b
b
Protection for users against indirect contacts
v
v
Additional protection for users against direct contacts (10 mA and 30 mA)
v
v
Protection for electrical installations against insulation faults (fire hazard, etc.)
v
v
Basic C60 circuit breakers retain their characteristics
b
b
Description
The Vigi earth leakage module is electromagnetic. It operates without an auxiliary
power supply. The C60 Vigi module combines the relay and toroid in a single unit.
These may not be fitted to 1 pole or 3 pole MCBs.
Instantaneous
It ensures instantaneous tripping (without time-delay).
Selective
s
Complete vertical discrimination is ensured if the following two conditions occur
simultaneously:
The downstream device is an instantaneous device and the upstream device is a
b
b
selective
s
or time-delay device
The sensitivity IDn of the downstream device is less than IDn/2 of the upstream
b
b
device
Combination
The C60 circuit breaker + C60 Vigi module combination constitutes a residual current
device in compliance with BS EN 60947-2 and BS EN 61009.
+
=
C60 circuit breaker
C60 Vigi module
Residual current device
C60 Vigi modules
Type AC A A si
A SiE
Applications
Current uses
b
Electronic loads, rectifiers, instruments, switch mode power supplies, variable speed controllers, etc...
-
b
b
b
Environment
Disturbed networks with:
Risk of nuisance
tripping due to
transient voltage
surges
Lightning stroke, switchgear operating
on the network...
b
b
b
b
High
risk of nuisance
tripping
Close lightning strokes, IT earthing
system, equipment incorporating
interference filters (lighting, computer
systems), variable speed controllers,
frequency converters, electronic
lighting ballasts
Enhanced
continuity
of supply
-
-
b
b
Sources of blindness Presence of harmonics or high
frequency rejections
Enhanced
earth
leakage
protection
-
-
b
b
Presence of DC components:
equipment incorporating diodes,
thyristors, triacs
-
-
b
b
Low temperatures
Use: -25 °C
-
b
b
b
Humid atmospheres and/or
atmospheres polluted by
aggressive agents
Swimming pools, marinas, agri-food industries, water
treatment plants, industrial production sites, etc...
-
-
-
b
Tripping
Due to sinusoidal AC
residual currents
Whether they are applied quickly or increased slowly
b
b
b
b
Due to continuous pulsed
residual currents
-
b
b
b
C60 Vigi modules
Instantaneous 10 to 1000mA
Selective
s
: 300mA and 1000mA
Earth leakage
protection