5/60
Technical
Section 9
Dimensions
Section 10
IC Astro
Technical data
Light sensitive
switches
5
Technical data
Memory:
14 switching operations (not including sunrise/sunset)
Minimum time between
1 min
2 switching operations:
Switching accuracy:
1 s
Time accuracy:
± 1 s /day
Programming longitude:
- 80° (East) to + 80° (West) in steps of 1°
Programming latitude:
-90° (South) to +90° (North) in steps of 1°
Operating temperature:
-20°C to +50°C
Degree of protection:
IP20B
Consumption:
override input: < 0.5 mA
Contact rating:
16 A under 250 V AC (cos
ϕ
= 1)
10 A under 250 V AC (cos
ϕ
= 0.6)
Function
The IC Astro astronomic programmable light sensitive switch is used to start
and stop an electric load (e.g. lighting) according to sunrise and sunset times,
without a brightness detector. Sunrise and sunset times are calculated
automatically by the IC Astro according to the geographic parameters configured
by the user.
Description
The IC Astro is configured according to the place of installation.
n
The place of installation of the IC Astro can be configured:
Either by selecting a country and a town
Or by its geographic coordinates (latitude, longitude)
n
The IC Astro allows:
Addition or deletion of a switch-off/switch-on switching operation (Off-On)
between the sunset and sunrise times
Different programmes each day
Difference in sunset and/or sunrise times, adjustable separately by ± 120 min.
according to local constraints (mountains, buildings, etc.)
Consideration of periods of absence (holidays), remote control of lighting
override by a NO contact
Re-initialisation of programmes
Automatic switching to “summer-winter” time
Permanent display by liquid crystals: hours and minutes, day of the week,
contact output status, and current programme
Manual waiver of the lighting On/Off programme, permanently or temporarily
(up to the next switching operation)
Type of lighting
Maximum power
Load table:
230 V incandescent and halogen lamps
2300 W
Non-corrected/ serial-corrected fluorescent tubes
26 x 36W, 20 x 58W,
with conventional ballast
10 x 100W
Parallel corrected fluorescent tubes
10 x 36W, 6 x 58W,
with conventional ballast
2 x 100W
Dual-mounted fluorescent tubes
10 x (2 x 58W),
with conventional ballast
5 x (2 x 100W)
Fluorescent tubes with electronic ballast
9 x 36W, 6 x 58W
Dual-mounted fluorescent tubes
5 x (2 x 36W),
with electronic ballast
3 x (2 x 58W)
Fluocompact lamps with electronic ballast
9 x 7W, 7 x 11W,
7 x 15W, 7 x 20W
Parallel-corrected mercury and sodium vapour lamps
250 W
Part numbers
Type
Language
Part number
IC Astro
gb, fr, es, it, de, pt
15223
Connection
n
Connection terminals: 1 screw connection per pole for cables up to 6 mm
2
On override
external contact
IC Astro
9933_Section_05.indd 60
12/08/2009 16: