5/59
IC2000P+
Technical data
Light sensitive
switches
Technical
Section 9
Dimensions
Section 10
Technical data
Adjustable brightness
Range 1 : 2 to 50 lx
threshold over 3 ranges:
Range 2: 60 to 300 lx
Range 3: 350 to 2100 lx
Time delay on contact
Separate setting between 20 s
closing and breaking:
and 40 s (80 s by default)
Contact:
Potential free.
Time base:
quartz.
Operating accuracy:
< ± 1 s / day at 20°C.
Number of separate
42
switching operations:
Minimum switching:
1 min
Switching accuracy:
1 s
Insulation class:
Class II
Degree of protection:
IP20B
Contact rating:
16 A under 250 V AC (cos
ϕ
= 1)
10 A under 250 V AC (cos
ϕ
= 0.6)
Load table:
Part numbers
Type
Part number
IC2000P+
15483
Function
The IC2000P+ controls lighting according to brightness and time. If brightness
drops below the set threshold (light sensitive function: IC) and if the time program
allows relay closing (time switch function), then the lighting circuit is activated.
Description
The IC2000P+ uses its time programming to define lighting On and Off periods:
n
According to three pre-set time programs:
“DAYPROG”: On time programming from 7 am to 8 pm a validation
of the IC function from 7 am to 8 pm
“NIGHTPROG”: On time programming from 5 am to 8 am and from 6 pm
to pm a validation of the IC function on these two operating periods
“EMPTYPROG”: Off time programming throughout the day a no validation
of the IC function. These programs can be modified if necessary
n
According to a customised operating period, with possibility of copying to the
other days. It is equipped with the following functions:
Consideration of periods of absence (holidays)
Temporary or permanent On or Off override
Remote control of lighting override by NO external contact
Consideration of change to “summer/winter” time, automatic or manual
Permanent liquid crystal display: of time and minutes
Wall mounted cell
(delivered with product and its fixing device)
n
Photoresistance, connection by 2-wire cable, 100 m max
Do not install parallel to mains cables
n
Degree of protection: IP54, IK05
n
Operating temperature: -40°C to +70°C
External input
n
Voltage: 230 V AC, + 10 %, - 15 %
n
Frequency: 50/60 Hz
n
Input current: max. 2.5 mA
n
Consumption: max. 0.4 mW
n
Cable length: max. 100 m
Connection
n
Connection terminals: 1 screw connection per pole for cables up to 6 mm
2
Type of lighting
Maximum power
230 V incandescent and halogen lamps
2300 W
Non corrected/serial corrected fluorescent tubes
26 x 36W, 20 x 58W,
with conventional ballast
10 x 100W
Parallel corrected fluorescent tubes
10 x 36W, 6 x 58W,
with conventional ballast
2 x 100W
Dual-mounted fluorescent tubes
10 x (2 x 58W),
with conventional ballast
5 x (2 x 100W)
Fluorescent tubes with electronic ballast
9 x 36W, 6 x 58W
Dual-mounted fluorescent tubes with electronic ballast 5 x (2 x 36W), 3 x (2 x 58W)
Fluocompact lamps with electronic ballast
9 x 7W, 7 x 11W,
7 x 15W, 7 x 20W
Parallel-corrected mercury and sodium vapour lamps
250 W
On override
external contact
Wall mounted cell
IC2000P+