IC2000
Technical data
Light sensitive
switches
Technical
Section 9
Dimensions
Section 10
Wall mounted cell - Part No. CCT15268
(delivered with product and its fixing device)
n
Cell connection: by double insulation 2-conductor cable, not to be laid next to
mains cables or water ducts, maximum length: 100 m
n
Horizontally orientable (90°)
n
Degree of protection: IP54, IK05
n
Operating temperature: -40°C to +70°C
Function
The light sensitive switch controls closing of a contact when brightness decreases
and drops below the selected threshold. It controls opening of a contact
when brightness increases and rises above the selected threshold.
Technical data
Adjustable brightness
2 to 2000 lux
threshold:
Time delay on contact
60 s
closing and breaking
Contact opening:
< 3 mm
Insulation class:
Class II
Degree of protection:
IP20B
Delivered with wall mounted cell and its fixing device
Contact rating:
16 A under 250 V AC (cos
ϕ
= 1)
10 A under 250 V AC (cos
ϕ
= 0.6)
Load table:
Type of lighting
Maximum power
230 V incandescent and halogen lamps
2300 W
Non-corrected/ serial-corrected/ dual mounted
2300 VA
fluorescent tubes with conventional ballast
Fluocompact lamps with conventional ballast
1500 VA
Non-corrected/ serial-corrected mercury
1000 VA
and sodium vapour lamps
Parallel-corrected mercury/ sodium vapour lamps
400 VA
and parallel-corrected fluorescent tubes
with conventional ballast
Fluorescent / dual-mounted fluorescent tubes
300 VA
with electronic ballast
Fluocompact lamps with electronic ballast
9 x 7W, 7 x 11W,
7 x 15W, 7 x 20W,
7 x 23W
Wall mounted cell