5/56
Technical
Section 9
Dimensions
Section 10
IC100, IC200
Technical data
Light sensitive
switches
5
Function
The light sensitive switch controls closing of a contact when brightness decreases
and drops below the selected threshold. It controls opening of a contact when
brightness increases and rises above the selected threshold.
Wall mounted cell - Part No. 15268
(delivered with product and its fixing device)
n
Cell connection: by double insulation 2-conductor cable, not to be laid next to
mains cables or water ducts, maximum length: 25 m for IC100
n
Degree of protection: IP54, IK05
n
Operating temperature: -40°C to +70°C
Switchboard cell
(delivered with product and its fixing device)
n
Delivered with 1 m cable
n
Degree of protection: IP65
n
Operating temperature: -40°C to +70°C
Technical data
IC100
Adjustable brightness
2 to 100 lux
threshold:
Time delay:
On closing: 20 s
On contact breaking: 80 s
Contact opening:
< 3 mm
Insulation class:
Class II
Degree of protection:
IP20B
Compatible with electrical distribution comb busbars
Delivered with wall mounted cell and its fixing device
Contact rating:
16 A under 250 V AC (cos
ϕ
= 1)
10 A under 250 V AC (cos
ϕ
= 0.6)
IC100 load table:
IC200
Adjustable brightness
2 to 200 lux
threshold:
Time delay on contact
> 40 s
closing and breaking:
Delivered with switchboard front face cell
Contact rating:
16 A under 250 V AC (cos
ϕ
= 1)
10 A under 250 V AC (cos
ϕ
= 0.6)
IC200 load table:
Type of lighting
Maximum power
230 V incandescent and halogen lamps
2300 W
Non-corrected/ serial-corrected/ dual mounted
2300 VA
fluorescent tubes with conventional ballast
Fluocompact lamps with conventional ballast
1500 VA
Non-corrected/ serial-corrected mercury
1000 VA
and sodium vapour lamps
Parallel-corrected mercury/ sodium vapour lamps
400 VA
and parallel-corrected fluorescent tubes
with conventional ballast
Fluorescent tubes/ dual mounted with electronic ballast 300 VA
Fluocompact lamps with electronic ballast
9 x 7W, 7 x 11W, 7 x 5W,
7 x 20W, 7 x 23W
Type of lighting
Maximum power
230 V incandescent, halogen lamps and fluocompact 2300 W
lamp with conventional ballast
Non-corrected/ serial-corrected fluorescent tubes
46 x 36W, 23 x 58W,
with conventional ballast
14 x 100W
Parallel-corrected fluorescent tubes
10 x 36W, 6 x 58W,
with conventional ballast
2 x 100W
Dual-mounted fluorescent tubes
11 x (2 x 58W),
with conventional ballast
6 x (2 x 100W)
Fluorescent tubes with electronic ballast
9 x 36W, 7 x 58W
Dual-mounted fluorescent tubes with electronic ballast 5 x (2 x 36W), 4 x (2 x 58W)
Fluocompact lamps with electronic ballast
6 x 7W, 8 x11W,
6 x 15W, 6 x 20W
Parallel-corrected mercury and sodium vapour lamps 250 W
Wall mounted cell
IC100
Switchboard cell
IC200