5/45
MINs and PRE switch-off warning
Technical data
Time management
Technical
Section 9
Dimensions
Section 10
Technical data
Two operating modes
Timer mode: time delay adjustable
triggered by switch on front face:
from 0.5 to 20 min
permanent mode: constant lighting
Pressing on a push-button renews the time delay
Voltage:
230 V AC +10 %, - 15%
Frequency:
50/60 Hz
Consumption during
< 6 VA
operation:
Consumption of connected
50 mA maximum
luminous pushbuttons:
Insulation class:
Class II
Degree of protection:
IP 20B
Operating temperature:
-25°C to +50°C
Contact rating:
6 A, cos
ϕ
= 1
Switch-off warning:
External via use of PRE product
Load table:
Functions
These timers allow closing and then opening of a contact in a determined time.
Type of lighting
Maximum power
230 V incandescent and halogen lamps
2300 W
Non-corrected/ serial-corrected/ dual mounted
2300 VA
fluorescent tubes with conventional ballast
Fluocompact lamps with conventional ballast
1500 VA
Parallel-corrected fluorescent tubes
400 VA (42
µ
F)
with conventional ballast
Fluorescent tubes with electronic ballast
300 VA
Fluocompact lamps with electronic ballast
9 x 7W, 7 x 11W, 7 x 5W,
7 x 20W, 7 x 23W
Connection
Connection terminals:
Screw connection per pole for cables up to 6 mm
2
Connection type:
3 or 4 wires with automatic selection of the control
push-button connection
Mechanical compatibility with electrical distribution comb busbars
L
N
MIN
4
N
R
P 3
PRE
3
A1 A2
4 wires
3
wires
L
N
MIN
4 N
P 3
R
4 wires
or
3 wires
MINs + PRE
Part numbers
Type
Part number
MINs
CCT15232
Technical data
Only to be used with the MIN et MINs timers
50% reduction in brightness during warning time
Time adjustable
from 20 to 60 s
Voltage:
230 V AC ± 10 %
Frequency: 50/60 Hz
Operating temperature:
-10°C to +50°C
Maximum power:
2300 W for incandescent lamps only.
Not compatible with fluorescent lamps, fluocompact lamps and very low voltage
halogen lamps
Connection
Connection terminals:
Screw connection per pole for cables up to 6 mm
2
Connection type:
3 or 4 wires
Functions
This is used in association with MIN or MINs timers and only on incandescent
lighting circuits (not used on fluorescent, fluocompact lamps and very low voltage
halogen lamps). It provides warning that the lighting is about to be switched off
by reducing the brightness by 50% during the 20 to 60 s warning time.
Part numbers
Type
Part number
PRE
15376
Specific terminal shield for MIN
15359
PRE switch-off warning
MINs
L
N
R
PRE
3
A1 A2