Section 10
MINp, MINt
Technical data
Time management
5
Type of lighting
Maximum power
230 V incandescent and halogen lamps
3600 W
Non-corrected/ serial-corrected/ dual mounted
3600 VA
(1)
fluorescent tubes with conventional ballast
Fluocompact lamps with conventional ballast
500 VA
(1)
Parallel-corrected fluorescent tubes
1200 VA (120 mF)
(1)
with conventional ballast
Fluorescent tubes with electronic ballast
1000 VA
Fluocompact lamps with electronic ballast
34 x 7W, 27 x 11W,
24 x 5W, 22 x 23W
(1) The ”switch-off warning” function is not available for these types of loads.
Technical data
Time delay adjustable from 0.5 to 20 min
Three operating modes triggered by switch on front face:
Timer mode with warning function built into the device.
The lamp blinks 40 and 30 s before the end of the time
delay
Timer mode mode without ”switch-off warning” function
Permanent mode : constant lighting
Timer mode operation:
Pressing a push-button for longer than 2 s: lighting will
last for 1 h
Pressing again a push-button for less than 2 s relaunch
the time delay of 1 h and pressing again a push-button
for more than 2 s switches off the light
For MINp, pressing a push-button for less than 2 s
launch the pre-set time delay, pressing again a push-
button for less than 2 s relaunch the pre-set time delay
For MINt, pressing a push-button for less than 2 s
launch the pre-set time delay, pressing again a push-
button for less than 2 s, switches off the light (impulse
relay mode)
Voltage:
230 V AC +10 %, - 15%
Frequency:
50/60 Hz
Consumption during operation: < 6 VA
Consumption of connected 50 mA maximum
luminous push-buttons:
Insulation class:
Class II
Degree of protection: IP 20B
Operating temperature: -25°C to +50°C
Contact rating:
6 A, cos
ϕ
= 1
Load table:
Functions
This timer allows closing and then opening of a contact in a determined time,
and it also provides warning that the lighting is about to be switched off by
flickering of the lamplight. (switch-off warning). The MINt timer is the same as MINp
with an “impulse relay” additional function (see ”MINt”).
Connection
Connection terminals:
1 screw connection per pole for cables up to 6mm
2
Connection type:
3 or 4 wires with selector switch on the side of the
product
Mechanical compatibility with electrical distribution comb busbars
L
N
4 N
L
3
R
4 Wires
or
3 Wires
Part numbers
Type
Part number
MINp
CCT15233
MINt
CCT15234