Background Image
Table of Contents Table of Contents
Previous Page  40 / 124 Next Page
Information
Show Menu
Previous Page 40 / 124 Next Page
Page Background

40

Protect

Circuit protection

Accessory

Padlocking device

b

b

Used to lock the toggle in the "open" or "closed" position by 4 mm diameter

padlock (not supplied).

b

b

The single-phase iC60H RCBO’s self-contained residual current device carries

out complete protection of final circuits:

v

v

protection against short-circuits and cable overloads

v

v

protection of persons against electric shock by direct contact

(10, 30 mA sensitivities),

v

v

protection of persons against electric shock by indirect contact

(100 mA sensitivity),

v

v

protection of equipment against fires set by leakage currents

(100 mA sensitivity).

b

b

The neutral is not interrupted when the device is tripped. Hence iC60H RCBO can

be used on most circuits, except for the ones operating under TT or IT earthing

systems.

IEC 61009-1,

IEC 61009-2-2,

BS EN 61009-1

AS/NZS 61009.1

Catalogue numbers

iC60H RCBO 10000

1P+N

A

Width in 9-mm

modules

B curve

Voltage rating (V)

Sensitivity (IΔn)

10 mA

30 mA

100 mA

DB405038

240

Rating

(In)

6 A

-

A9D31806

-

2

10 A

-

A9D31810

-

16 A

-

A9D31816

-

20 A

-

A9D31820

-

25 A

-

A9D31825

-

32 A

-

A9D31832

-

40 A

-

A9D31840

-

45 A

-

A9D31845

-

C curve

Voltage rating (V)

Sensitivity (IΔn)

10 mA

30 mA

100 mA

DB405038

110

Rating

(In)

10 A

-

A9D19810

-

2

16 A

-

A9D19816

-

20 A

-

A9D19820

-

25 A

-

A9D19825

-

32 A

-

A9D19832

-

240

Rating

(In)

6 A

A9D10806

A9D11806

A9D12806

10 A

A9D10810

A9D11810

A9D12810

16 A

A9D10816

A9D11816

A9D12816

20 A

A9D10820

A9D11820

A9D12820

25 A

A9D10825

A9D11825

A9D12825

32 A

A9D10832

A9D11832

A9D12832

40 A

A9D10840

A9D11840

A9D12840

45 A

A9D10845

A9D11845

A9D12845

Operating frequency

50…60 Hz

Accessory

Type

Padlocking device (bag of 10 pieces)

A9A27049

iC60H RCBO

10, 30 and 100 mA

Alternating current (AC) 50/60 Hz

Breaking capacity (Icn) according to IEC 61009-1

Voltage (Ue)

Ph/N

110 V

240 V

Rating (In)

6 to 45 A

10000 A

10000 A