Background Image
Table of Contents Table of Contents
Previous Page  31 / 124 Next Page
Information
Show Menu
Previous Page 31 / 124 Next Page
Page Background

Acti 9 Isobar

the safest distribution board

Acti9 Isobar B type

distribution boards

Main characteristics Acti9 Isobar IP55

According to BE EN 61439-3

230/240v

400v

415v

Withstand

conditional

25kA

25kA

25kA

unconditional

25kA/50mS

25kA/50mS

25kA/50mS

17kA/200mS

17kA/200mS

17kA/200mS

insulation voltage (Ui)

500vAC

Pollution degree

3

Rated inpulse withstand voltage (Uimp)

6kV

Current rating (A)

100A

Degree of protection

External IP30 or IP55

(IEC 60529)

Internal IP20

Endurance (O-C) Isobar switch

disconnector

3000

Overvoltage category

IV

Operating temperature

-35 to +70

0

C

Storage teperature

-40 to +80

0

C

Catalogue numbers

Acti9 Isobar Standard IP55 distribution boards busbar rating 125amp steel door

No of TP ways

No of SP ways

No of DP ways

SEA9BN6HDGR

6

18

9

SEA9BN8HDGR

8

24

12

SEA9BN12HDGR

12

36

18

SEA9BN16HDGR

16

48

24

Acti9 Isobar Standard IP55 distribution boards busbar rating 125amp transparent door

No of TP ways

No of SP ways

No of DP ways

SEA9BN6HDGK

6

18

9

SEA9BN8HDGK

8

24

12

SEA9BN12HDGK

12

36

18

SEA9BN16HDGK

16

48

24

Weight (kG) - Dimensions (mm)

Standard

Meter ready

Split load kG

Height

width

depth

4 way

n

n

9

484

470

139

6 way

6 way

n

10.5

484

470

138

8 way

6 way

n

11

538

470

138

12 way

12 way

n

13.5

700

470

139

16 way

16 way

n

16

808

470

139

18 way

18 way

n

16.2

862

470

139

24 way

24 way

n

22

1024

139

n

n

all versions

28

1294

470

139

250 amp incoming

section

4

400

470

130

IP55

kG

Height

width

depth

6 way

b

b

32.4

650

600

330

8 way

b

b

32.9

650

600

330

12 way

b

b

40.1

800

600

330

16 way

b

b

41.4

800

600

330

31