![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0031.png)
Acti 9 Isobar
the safest distribution board
Acti9 Isobar B type
distribution boards
Main characteristics Acti9 Isobar IP55
According to BE EN 61439-3
230/240v
400v
415v
Withstand
conditional
25kA
25kA
25kA
unconditional
25kA/50mS
25kA/50mS
25kA/50mS
17kA/200mS
17kA/200mS
17kA/200mS
insulation voltage (Ui)
500vAC
Pollution degree
3
Rated inpulse withstand voltage (Uimp)
6kV
Current rating (A)
100A
Degree of protection
External IP30 or IP55
(IEC 60529)
Internal IP20
Endurance (O-C) Isobar switch
disconnector
3000
Overvoltage category
IV
Operating temperature
-35 to +70
0
C
Storage teperature
-40 to +80
0
C
Catalogue numbers
Acti9 Isobar Standard IP55 distribution boards busbar rating 125amp steel door
No of TP ways
No of SP ways
No of DP ways
SEA9BN6HDGR
6
18
9
SEA9BN8HDGR
8
24
12
SEA9BN12HDGR
12
36
18
SEA9BN16HDGR
16
48
24
Acti9 Isobar Standard IP55 distribution boards busbar rating 125amp transparent door
No of TP ways
No of SP ways
No of DP ways
SEA9BN6HDGK
6
18
9
SEA9BN8HDGK
8
24
12
SEA9BN12HDGK
12
36
18
SEA9BN16HDGK
16
48
24
Weight (kG) - Dimensions (mm)
Standard
Meter ready
Split load kG
Height
width
depth
4 way
n
n
9
484
470
139
6 way
6 way
n
10.5
484
470
138
8 way
6 way
n
11
538
470
138
12 way
12 way
n
13.5
700
470
139
16 way
16 way
n
16
808
470
139
18 way
18 way
n
16.2
862
470
139
24 way
24 way
n
22
1024
139
n
n
all versions
28
1294
470
139
250 amp incoming
section
4
400
470
130
IP55
kG
Height
width
depth
6 way
b
b
32.4
650
600
330
8 way
b
b
32.9
650
600
330
12 way
b
b
40.1
800
600
330
16 way
b
b
41.4
800
600
330
31