![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0108.jpg)
108
Technical advice
Circuit breakers for direct
current applications (cont.)
24 V - 48 V direct current applications
24 V DC generator power supply protection
b
b
Earthed network:
v
v
Isc = 10 kA / In = 63 A,
v
v
Isc = 10 kA / In = 20 A.
Solution
iC60H 2P 63 A + iC60N 2P 20 A + DC loads
DB124262
In
1
In
2
Isc
1
AC network
Load 1
Isc
2
DC network
Load 2
Load 3