Background Image
Table of Contents Table of Contents
Previous Page  331 / 408 Next Page
Information
Show Menu
Previous Page 331 / 408 Next Page
Page Background

11

11/17

Dimensions

Section 12

Influence of ambient

temperature (cont.)

Technical advice

DB123331

Spacer cat. no. A9A27062

Switches

b

b

In all cases, the switches are correctly protected against overloads by a circuit

breaker with a lower or equal rating, operating at the same ambient temperature.

iCT contactors

In the case of contactor mounting in an enclosure for which the interior temperature

is in a range between 50°C and 60°C, it is necessary to use a spacer,

cat. no. A9A27062, between each contactor.

Splitter blocks

In the event of a temperature higher than 40°C, the maximum acceptable current is

limited to the values in the table below:

Type

Temperature

40°C 45°C 50°C 55°C 60°C

Multiclip 80 A

80

76

73

69

66

Distribloc 63 A

63

60

58

55

53