11
11/9
Dimensions
Section 12
Tripping curves (cont.)
According to IEC/EN 60947-2 standards
Technical advice
iC60N/H/L
According to IEC/EN 60947-2 (reference temperature 50°C)
Curves B, C, D rating up to 4 A
Curves Z, K rating up to 4 A
DB124184
t(s)
0,01
0,1
1
10
100
1000
I / In
1
B C D
5.7
±20%
11.3
±20%
17
±20%
DB124450
I / In
t(s)
0,01
0,1
1
10
100
1000
K
Z
1
4.2
±20%
17
±20%
Curves B, C, D rating 6 A to 63 A
Curves Z, K rating 6 A to 63 A
DB124188
t(s)
0,01
0,1
1
10
100
1000
I / In
B C D
1
5.7
±20%
11.3
±20%
17
±20%
DB124451
I / In
t(s)
0,01
0,1
1
10
100
1000
K
Z
1
4.2
±20%
17
±20%
3600 s
for
I/In = 1.05
3600 s for I/In = 1.3
3600 s
for
I/In = 1.05
3600 s for I/In = 1.3
3600 s for I/In = 1.3
3600 s
for
I/In = 1.05
3600 s for I/In = 1.3
3600 s
for
I/In = 1.05
Direct current