Background Image
Table of Contents Table of Contents
Previous Page  274 / 408 Next Page
Information
Show Menu
Previous Page 274 / 408 Next Page
Page Background

9

9/4

Technical

Section 11

Dimensions

Section 12

Wall mounted switchgear

Earth leakage

Extension boxes

Safepact 2

Application

n

The vigi earth leakage module option disconnects the circuit breaker when an

electrical earth fault is detected

n

Used to overcome high earth fault loop impedance and associated excessive

disconnection times eg long cable runs

n

Enhanced personal and equipment protection

Technical data

Adjustable sensitivity and

time delay settings

For discrimination with other RCDs

Protection against nuisance

tripping due to transient

overvoltages etc.

To IEC255-4 and IEC801-2 - 5

Class A

Immunity to DC components of up to 6mA

Remote indication of tripping

Using optional changeover contact SDV

Rating

Sensitivity settings (A)

Up to 160A

0.03*, 0.3, 1, 3 and 10

200 - 250

0.03*, 0.3, 1, 3, and 10

400 - 630

0.3, 1, 3, 10 and 30

Time delay settings (ms)

0, 60, 150 and 310

* If the sensitivity is set to 30mA there is no time delay whatever the time delay

setting. For ordering references see previous pages.

Extension boxes

n

Provide extra cabling space when using oversized cables. Colour RAL9001

Size

To fit rating

Part number

100mm

63 - 250A

MGEX160C

200mm

63 - 250A

MGEX250C

120mm

400 - 630A

MGEX630C

Intelligent Safepact

n

The Safepact range has now been extended to include our new Micrologic

control units up to 630 amp, each unit is supplied complete and ready to

install all the customer has to do is connect the supply, load and interface to

the modbus system.

Application

n

The Individual protection or isolation of loads

n

Monitoring of loads with Micrologic 5 control unit

n

Separate incomer to distribution equipment

n

Replacement to Fuse Switches

Range Reference

Part number

Safepact 4 pole 40A mccb Micrologic 5

MGE0404M5

Safepact 4 pole 100A mccb Micrologic 5

MGE1004M5

Safepact 4 pole 160A mccb Micrologic 5

MGE1604M5

Safepact 4 pole 250A mccb Micrologic 5

MGE2504M5

Safepact 4 pole 400A mccb Micrologic 5

MGE4004M5

Safepact 4 pole 630A mccb Micrologic 5

MGE6304M5

Technical data

Ingress protection

IP42

Operational Voltage

415V

Ultimate breaking capacity

70kA

Rated service breaking capacity 100%

FDM module fitted and wired

Modbus inferface, power supply and protection fitted and wired