2/9
Our empty enclosures are marked CE according to the Low-Voltage Directive (LVD).
It is the responsibility of the final equipment manufacturer to respect the regulations
in force.
Technical characteristics
Protection degree:
● IP 66 for the single-door enclosures and IP 55 for the double-door enclosures,
according to IEC 60529.
● Nema Type 4, 4X for the single-door enclosures and Nema Type 12, 12K, 13 for
the double-door enclosures according to NEMA 250 standard.
Resistance to external mechanical impacts:
● IK 10 for the plain-door enclosures, according to IEC 62262.
● IK 08 for the glazed-door enclosures.
Mechanical characteristics
Fixing of mounting accessories
● 4 (or 6**) M8 25 shouldered backstuds for installing mounting plates and step
slides, leaving a space of 10 mm behind them.
** 6 studs for widths 1000 and 1200.
Personnel protection
Earth connection:
Spacial S3D steel enclosures are equipped with M6 16 earth
studs welded in the body and the door for equipotential connection. Earth braid to
be ordered separately (see page
7/139
).
Closing the enclosure:
the enclosures are equipped from the height of 600 mm
with three locking points with linkage, with a single control point, preventing the
enclosures from being left ajar. Locks and inserts, page
2/30
.
Coating properties
Colour:
RAL 7035 grey; finish: structured.
Coating thickness:
60 μm.
Fire class:
M0.
Resistance to corrosion:
compliance with standard IEC 62208 for outdoor
installation: 288 h of humid heat and 336 h of salt mist.
Note:
the Spacial S3D is specially designed for indoor installations. For outdoor
installations, it is advisable to install a canopy or consult us.
Nuclear decontamination:
RAL 7035 and AFNOR A550 tests available on
demand.
*
For further
information, see the
Technical Annexes on
page
9/1
.
02_009_S3D008.indd 9