Page 648 - 0700-schn-encl-10

Basic HTML Version

8/67
Electronic control
Reference
NSYCUE1100W230L NSYCUE1400W230L NSYCUE1400W400L NSYCUE1800W400L
Voltage
230 V; 50/60 Hz
3 400 V; 50 Hz / 3 440 V; 60 Hz
Cooling power (50/60 Hz) according to EN 14511
L35-L35
L35-L50
1100/1200 W
(3755/4097 Btu/h)
880/930 W
(3004/3175 Btu/h)
1400/1500 W
(4780/5121 Btu/h)
1200/1300 W
(4097/4438 Btu/h)
1400/1500 W
(4780/5121 Btu/h)
1200/1300 W
(4097/4438 Btu/h)
1800/1900 W
(6145/6485 Btu/h)
1400/1500 W
(4780/5121 Btu/h)
Dimensions
Height
Width
Depth
1,010 mm
400 mm
240 mm
Intensity
Starting current
Rated current
12.1/13.9 A
3.2/3.7 A
18.1/22.2 A
4.8/5.8 A
3.7/4.3 A
1.2/1.4 A
5.3/6.3 A
1.8/2.1 A
Power cunsumption absorbed
L35-L35
L35-L50
600/690 W
690/790 W
900/1,100 W
1100/1300 W
700/810 W
810/930 W
1000/1200 W
1200/1400 W
Energy efficiency ratio (EER)
L35-L35
1.8/1.7
1.6/1.4
2.0/1.9
1.8/1.7
Control type
Electronic controller
Temperature setting range
+20...+50 °C
Maximum outside temperature
55 °C
Noise level
62 dB (A)
64 dB (A)
66 dB (A)
69 dB (A)
Air flow
of the internal circuit
of the external circuit
575/600 m
3
/h
860/900 m
3
/h
860/900 m
3
/h
860/900 m
3
/h
860/900 m
3
/h
860/900 m
3
/h
885/900 m
3
/h
1050/1160 m
3
/h
Type of zero-potential alarm
Inverter contact
Weight of unit
45 kg
46 kg
47 kg
50 kg
Cooling gas type
R134a (0.85 kg)
R134a (0.85 kg)
R134a (0.85 kg)
R134a (0.85 kg)
IP (IEC 60529)
On the internal circuit
On the external circuit
54
34
External circuit filter
Option
Assembly
Side
Thermal protection recommended
(fuse melt curve)
T6A
T8A
T2A
T3A